HX7+ ASD Installation and Operation Manual
HX7+ ASD Characteristics
Over-Current Protection
Each
HX7+ ASD
model was designed for a specified operating power range. The HX7+ ASD will incur a
trip if the design specifications are exceeded.
However, the HX7+ ASD may be operated at 120% of the specified output-current range for a limited
amount of time as indicated in the section titled
Voltage/Current and Thermal Specifications on pg. 230
Also, the
) may be adjusted to help with nuisance over-current trips.
When using the HX7+ ASD for an application that controls a motor which is rated significantly less than
the maximum current rating of the HX7+ ASD, the over-current limit setting will have to be changed to
match the application. See
Electronic Thermal Protection #1
for further information on this ASD/motor
configuration.
HX7+ ASD Capacity
The
HX7+ ASD
must not be used with a motor that has a significantly larger capacity, even if the motor is
operated under a small load. An HX7+ ASD being used in this way will be susceptible to a high-output
peak current which may result in nuisance tripping.
Do not apply a level of input voltage to an HX7+ ASD that is beyond that which the HX7+ ASD is rated.
The input voltage may be stepped down when required with the use of a step-down transformer or some
other type of voltage reduction system.
Using Vector Control
Using
Vector Control
enables the system to produce very high torque over the entire operating range
even at extremely low speeds.
Vector Control
may be used with or without feedback. However, using
feedback increases the speed accuracy for applications requiring precise speed control. Enabling the
Automatic Energy Savings
further increases the efficiency of the
HX7+ ASD
while maintaining its
robust performance.
Vector Control
is not capable of operating multiple motors connected in parallel.
See
for further information on using
Vector Control
.
Local
|
Remote Operation
While running in the
Local
mode at a non-zero speed, if the RJ45 connector is removed from the
keypad
,
the
HX7+ ASD
remains in the
Local
mode running at the last commanded speed even though the
Local|Remote
LED is off. The HX7+ ASD output remains at the frequency of the
field at the time of the disconnect for the duration of the disconnect.
Once reinserted, the reference frequency goes to zero hz.
To prevent this condition, before disconnecting the RJ45 connector, ensure that the HX7+ ASD is off.
CAUTION
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...