180
HX7+ ASD Installation and Operation Manual
Hz Per User-Defined Unit
Program
Utility Parameters
Display Units
This parameter allows the user to input a quantity to be displayed on the keypad
that is proportional to the output frequency of the drive.
This feature is useful when the output of a process is moved along at a rate that
is proportional to the output frequency of the drive.
Direct Access Number — F702
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.0
Units — Hz/UDU
Frequency Display Resolution
Program
Utility Parameters
Display Units
The parameter sets the number of decimal places to be displayed during non-
Accel/Decel
functions.
Settings:
0 — 1
1 — 0.1
2 — 0.01
Direct Access Number — F703
Parameter Type —
Numerical
Factory Default —
0.1
Changeable During Run —
Yes
Minimum — 1
Maximum — 0.01
Accel/Decel Special Display Resolution
Program
Special Control
Accel/Decel Special
This parameter sets the number of decimal places to be displayed for
Accel/
Decel
functions.
Direct Access Number — F704
Parameter Type —
Numerical
Factory Default —
0.1
Changeable During Run —
Yes
Minimum — 1
Maximum — 0.01
Prohibit Initializing User Parameters During Typeform
Initialization
Program
Special Control
Special Parameters
This parameter
Enables/Disables
the ability to initialize user parameters during
a
Type Form
initialization.
Settings:
0 — Allowed
1 — Prohibited
Direct Access Number — F709
Parameter Type —
Selection List
Factory Default —
Allowed
Changeable During Run —
Yes
V/f Group
No path available (Direct Access Only)
While operating using the
CN8 Option
(LED Keypad)
1 of 4
V/f
groups
may be selected and run. Each
V/f
group is comprised of 4 user-defined
variables:
Base Frequency
,
Base Frequency Voltage
,
Manual Torque Boost
,
and
Electronic Thermal Protection
.
Settings:
1 — Group 1
2 — Group 2
3 — Group 3
4 — Group 4
Note:
Press
ESC
from the
screen to access this
parameter.
Direct Access Number — F720
Parameter Type —
Selection List
Factory Default —
1
Changeable During Run —
Yes
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...