HX7+ ASD Installation and Operation Manual
OUT6 Off Delay
Program
Terminal Selection
Out Terminal Delays
This parameter delays the opening of the
OUT6
output terminals by the
programmed value (see waveforms at
The delay may be increased to allow the devices that are connected to
OUT6
to
respond.
Direct Access Number — F165
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT7 Off Delay
Program
Terminal Selection
Out Terminal Delays
This parameter delays the opening of the
OUT7
output terminals by the
programmed value (see waveforms at
The delay may be increased to allow the devices that are connected to
OUT7
to
respond.
Direct Access Number — F166
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Motor #2 Base Frequency
Program
Motor Parameters
Motor Set #2
The
Motor #2
Base Frequency
setting is the frequency at which the output
voltage of the ASD reaches its maximum setting. The
#2 Maximum Output
Voltage
This parameter is used only when the parameters for motor set
#2
are
configured and selected.
Motor set
#2
may be selected by a properly configured
input terminal.
For proper motor operation, the
Base Frequency
should be set for the name-
plated frequency of the motor.
Direct Access Number — F170
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Motor #2 Max Output Voltage
Program
Motor Parameters
Motor Set #2
The
Motor #2 Maximum Output Voltage
is the
Motor
#2
output voltage at
the
Base Frequency
). Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the
Supply Voltage Compensation
setting (
This parameter is used only when the parameters for motor set
#2
are
configured and selected. Motor set
#2
may be selected by a properly configured
input terminal.
Direct Access Number — F171
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts
Motor #2 Torque Boost
Program
Motor Parameters
Motor Set #2
The
Motor #2 Torque Boost
function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the
#2
Base Frequency
setting
(
).
See parameter
Motor #1 Torque Boost
) for an explanation of torque
boost.
This parameter is used only when the parameters for motor set
#2
are
configured and selected. Motor set
#2
may be selected by a properly configured
input terminal.
Direct Access Number — F172
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...