HX7+ ASD Installation and Operation Manual
93
OUT1 Off Delay
Program
Terminal Selection
Out Terminal Delays
This parameter delays the opening of the
OUT1
(
A
&
C
) output terminals by
the programmed value.
The delay may be increased to allow the devices that are connected to
OUT1
to
respond.
Direct Access Number — F160
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT2 Off Delay
Program
Terminal Selection
Out Terminal Delays
This parameter delays the opening of the
OUT2
(
A
&
C
)
output terminals by
the programmed value (see waveforms at
The delay may be increased to allow the devices that are connected to
OUT2
to
respond.
Direct Access Number — F161
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
FL Off Delay
Program
Terminal Selection
Out Terminal Delays
This parameter delays the opening of the
FL
output terminals by the
programmed value (see waveforms at
The delay may be increased to allow the devices that are connected to
FL
to
respond.
Direct Access Number — F162
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT4 Off Delay
Program
Terminal Selection
Out Terminal Delays
This parameter delays the opening of the
OUT4
output terminals by the
programmed value (see waveforms at
The delay may be increased to allow the devices that are connected to
OUT4
to
respond.
Direct Access Number — F163
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT5 Off Delay
Program
Terminal Selection
Out Terminal Delays
This parameter delays the opening of the
OUT5
output terminals by the
programmed value (see waveforms at
The delay may be increased to allow the devices that are connected to
OUT5
to
respond.
Direct Access Number — F164
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...