Hydro Unit
Installation Manual
■
Wire the remote controller
Wiring diagram
Terminal block (TB04) for the remote control wiring on
the Hydro Unit
Second remote controller installation
requirements
Installation
For a dual remote controller system, install the remote
controllers in the following way.
1. Set one of remote controllers as the header
remote controller. (Remote controller of Hydro
Unit is preset as Header.)
2. Set from “Header / Second” in “Initial setting” on
the setting screen.
• To control room temperature instead of water
temperature with this remote controller, set DN “40”
of Hydro Unit to “1”.
Basic wiring diagram
NOTE
Terminals of A and B have no polarity.
To diverge from the Hydro Unit
A
B
A
B
Remote control wiring (procured locally)
Terminal block for the
remote control wiring
Remote
controller
* Terminals of A and B
have no polarity.
* Use wire of 0.5 mm
2
to 2.0 mm
2
.
* A crimp-style terminal cannot be used.
A B
A B
A B
Remote control
wiring (Locally
procured)
0.5 mm
2
to 2.5 mm
2
.
Remote controller
(Header)
Remote controller
(Second)
(Sold
separately)
Terminal block (TB04)
for the remote control
wiring
Earth
Hydro Unit
■
Central Remote Controller (option)
To connect the Central Controller and BMS (TU2C-LINK)
CN902 for the central remote control wiring on the Hydro Unit PCB
Communication wiring and central control wiring use 2-core non-polarity wires.
Use 2-core shield wires to prevent noise trouble.
In this case, for the system grounding, close (connect) the end of shield wires, and isolate the end of terminal.
When connecting and controlling the system controller, the central control address (DN03) setting is required.
On some system controllers, DN03 may be set automatically.
For details, refer to the manual of the system controller used and the installation manual.
Item
DN
Details
Central control address
03
1 ~ 128
1
2
Hydro Unit
main PCB
Remote controller
Connection
point
(Optional parts)
TCB-KBCN32VEE
White
Locally procured
(Terminal block, connector, etc.)
Red
Blue
50
cm
Locally procured
2-core, non-polarity, Shielded wire type
Size : Total Length
1.0 to 1.5 mm
2
: Up to 1000 m
2.5 mm
2
:
Up to 2000 m
Central
Remote
Controller
CN903
CN902