– 13 –
Hydro Unit
Owner’s Manual
General Specifications
Single Phase model
3 Phase model
80 class
112,140,160 class
Outdoor unit
HWS-804H-E1
HWS-1104H-E1
HWS-1404H-E1
Power supply
220-230 V ~ 50 Hz
Type
INVERTER
Function
Heating & Cooling
Heating
Capacity
(kW)
8.0
11.2
14.0
Input
(kW)
1.79
2.30
3.11
COP
4.66
4.88
4.50
Cooling
Capacity
(kW)
6.0
10.0
11.0
Input
(kW)
1.94
3.26
3.81
EER
3.10
3.07
2.89
Refrigerant
R410A
Dimension
HxWxD
(mm)
890x900x320
1,340x900x320
Outdoor unit
with Cord heater
HWS-
1104H8-E1
HWS-
1404H8-E1
HWS-
1604H8-E1
HWS-
1104H8R-E1
HWS-
1404H8R-E1
HWS-
1604H8R-E1
Power supply
380-400 V 3N~ 50 Hz
Type
INVERTER
Function
Heating & Cooling
Heating
Capacity
(kW)
11.2
14.0
16.0
11.2
14.0
16.0
Input
(kW)
2.34
3.16
3.72
2.34
3.16
3.72
COP
4.80
4.44
4.30
4.80
4.44
4.30
Cooling
Capacity
(kW)
10.0
11.0
13.0
10.0
11.0
13.0
Input
(kW)
3.26
3.81
4.80
3.26
3.81
4.80
EER
3.07
2.89
2.71
3.07
2.89
2.71
Refrigerant
R410A
Dimension
HxWxD
(mm)
1,340x900x320
Cord heater
(W)
–
75
Hydro Unit
HWS-804XWHM3-E1
HWS-804XWHT6-E1
HWS-804XWHT9-E1
Back up heater capacity
3.0
6.0
9.0
Power supply
for back up heater
220-230 V~ 50 Hz
380-400 V 3N~ 50 Hz
380-400 V 3N~ 50 Hz
for hot water cylinder heater
(option)
220-230 V~ 50 Hz
Leaving water
temperature
Heating
(°C)
20-55
Cooling
(°C)
7-25
Hydro Unit
HWS-1404XWHM3-E1
HWS-1404XWHT6-E1
HWS-1404XWHT9-E1
Back up heater capacity
3.0
6.0
9.0
Power supply
for back up heater
220-230 V~ 50 Hz
380-400 V 3N~ 50 Hz
380-400 V 3N~ 50 Hz
for hot water cylinder heater
(option)
220-230 V~ 50 Hz
Leaving water
temperature
Heating
(°C)
20-55
Cooling
(°C)
7-25
13-EN