GX9 ASD Installation and Operation Manual
85
ST Signal Selection
Program
Terminal
Input Special Functions
This parameter is used to set the operation of the
Standby
(
ST
) control terminal
or any terminal configured as the
ST
terminal.
Settings:
0 — Standard
1 — Always On
2 — Interlock with F/R Terminals
The
Standard
setting enables the ASD for operation so long as the control
terminal
ST
is connected to
CC
via a jumper, contact, or other means.
The
Always On
setting allows the ASD to operate without the
ST
-to-
CC
connection. The control terminal
ST
may be configured for another function or
unused.
The
Interlock with F/R Terminal
setting configures the
F
(
Forward
) and
R
(
Reverse
) control terminals for the secondary function of
Standby
. Closing a
set of contacts to either
F
or
R
will cause the ASD to accelerate the motor to the
programmed setpoint of
F
or
R
. Opening the
F
and
R
contact will disable the
ASD and the motor will coast to a stop. The control terminal
ST
may be
configured for another function or unused.
Direct Access Number — F103
Parameter Type —
Selection List
Factory Default —
Standard
Changeable During Run —
No
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......