6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 972 -
5.6.4
Monitoring jacks
A monitoring jack including a LED is provided so that the user can monitor a binary signal on
the logic straightforwardly. For example, when the user wishes to monitor the operating state
of a relay function, set the signal number (Data ID) that the user wishes to monitor; then the
user can see lighting the LED when the relay is operated. Using with an oscilloscope, the user
can also observe the binary signal that comes from the monitoring jack; three monitoring jacks
(Term A, B, and C) are available on the front panel.
Table 5.6-9 Output terminals for signal monitoring (No default setting)
Jack
Jack name
LED Color
Remarks
A
Term A
Yellow
Set user’s preferred signal number
B
Term B
Yellow
Set user’s preferred signal number
C
Term C
Yellow
Set user’s preferred signal number
When the user wishes to test the phase-A element the OC1 relay using an oscilloscope,
for example, set the phase-A monitoring point (
44001 8000011C20
†) for the setting [
Term A
],
as shown in Figure 5.6-5. Consequently, the OC1 operating signal is outputted to the jack at
the Term A. The LED at the Term A is also lit in step with the output signal. The user can use
to monitor the phase-B and phase-C signals using by settings respective Data IDs for the [
Term
B
] and [
Term C
]. We shall see the menus for the Term A to Term C in Chapter
User interface:
Test sub-menu: Signal monitoring screen.
OC function
(Function ID: 440001)
DRIVER
Term
A
Signal designated by
setting [
Term A
]
Signal to the
oscilloscope
“TEST-A”
(201B01
_
3100221001)
Monitoring jack (Function ID: 201301)
Jacks and LEDs
Term A LED
440001 8200011C22
440001 8000011C20
440001 8100011C21
A
B
C
OC1
DRIVER
Term
B
Signal designated by
setting [
Term B
]
Signal to the
oscilloscope
“TEST-B”
(201B01
_
3100231001)
Term B LED
DRIVER
Term
C
Signal designated by
setting [
Term C
]
Signal to the
oscilloscope
“TEST-C”
(201B01
_
3100241001)
Term C LED
Figure 5.6-5 Monitoring logics A, B and C
†Note: The monitoring point is just selected for the explanation; the user can select a
monitoring point from the relay applications and the control and monitoring
applications. The monitoring points is listed as PLC monitoring points in each
function.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......