Table 4.1-19 PLC monitoring points (signals with in operate logic)
Signal Number
Signal Name
Description
510001 8101011E82
SPOS01_OEC_OK_CS SPOS01 on direction execute command
510001 8101021E82
SPOS02_OEC_OK_CS SPOS02 on direction execute command
510001 8101031E82
SPOS03_OEC_OK_CS SPOS03 on direction execute command
…
….
….
510001 8101141E82
SPOS20_OEC_OK_CS SPOS20 on direction execute command
510001 8001011E81
SPOS01_FEC_OK_CS
SPOS01 off direction execute command
510001 8001021E81
SPOS02_FEC_OK_CS
SPOS02 off direction execute command
510001 8001031E81
SPOS03_FEC_OK_CS
SPOS03 off direction execute command
…
…
…
510001 8001141E81
SPOS20_FEC_OK_CS
SPOS20 off direction execute command
Table 4.1-20 PLC monitoring points (Output signal for response)
Signal Number
Signal Name
Description
510001 8601011E91
SPOS01_EX_FFL
SPOS01 execute fail signal by fixedlogic
510001 8601021E91
SPOS02_EX_FFL
SPOS02 execute fail signal by fixedlogic
510001 8601031E91
SPOS03_EX_FFL
SPOS03 execute fail signal by fixedlogic
….
….
….
510001 8601141E91
SPOS20_EX_FFL
SPOS20 execute fail signal by fixedlogic
(ix)
Setting names
Note: The “xx” of “SPOSxx” represents the SPOS function number. (e.g., if the SPOS03
is considered, the “xx” is equal to “03”. The suffix “xx” can be represented by either
a “01” to “20”).
Table 4.1-21 Setting of Operate in SPOSxx
Setting Name
Description
Default
Setting item or value
SPOSxx-PLSM
Method of command output(SPOS01-20)
Fix
Fix/Var/Latch
SPOSxx-CPW
Duration of command output(SPOS01-20)
1.0[sec]
0.1~50.0[sec]
SPOSxx-RST
Detection time for terminating control (SPOS01-20)
30.0[sec]
0.1~100.0[sec]
SPOSxx-LGCTRCON
Logic selector for operate condition (SPOS01-20)
Fixedlogic
Fixedlogic/PLC
SPOSxx-LGCFEXOT
Logic selector for command output (SPOS01-20)
Fixedlogic
Fixedlogic/PLC
SPOSxx-CTREN
Activate control function of SPOS01-20
On
Off / On
SPOSxx-LGEXFFCT
Logic selector for operate condition (SPOS01-20)
Fixedlogic
Fixedlogic / PLC
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...