6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 528 -
2.
Set scheme switch [
SPOS01-LGEXFFCT
] to
Fixedlogic.
Replacing the original logic
If the user wishes to replace the operate condition logic completely, it can be achieved using
PLC connection point “User configurable condition”:
1.
Connect the user-customized logic using “SPOS01IN_TMP_41”, listed as PLC#2 in
Table 4.1-17.
2.
Set scheme switch [
SPOS01-LGEXFFCT
] to
PLC
.
Note: The user must program PLC logic “Control hierarchy condition”. The Control
hierarchy condition to be provided with the user-programmed PLC logic may be
43R/L; it may be connected using PLC connection point “SPOS01IN_TMP_28” in
Note: The output of the operate condition logic is provided separately for On-execution
and for Off-execution. To see the outputs, refer to Table 4.1-18.
Operate condition
User configurable operate condition (PLC#2 connection
point)
Same Directional
Controlling Event
OFF
[SCDEN]*8
Fixedlogic
[
SPOS01-
LGEXFFCT
]
To selection logic
Control hierarchy (e.g. 43RL) (PLC connection point)*9
[
SPOS01-CTREN
]
On
Additional condition (PLC#1 connection point)
SPOS01IN_TMP_31
510001 800101EE61
SPOS01IN_TMP_41
510001 810101EE66
SPOS01IN_TMP_28
510001 820101ED50
Command
“ON-control” received
Command
“OFF control” received
received
&
&
&
&
&
&
1
≥
1
≥
SPOS01_STATE
SPOS01 function (Function ID: 510001)
Function
“Automatic sequence control” is in progress
CBK_STATE
Command blocking
*
1
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
Tripping
*
4
(“General trip”)
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
GEN. TRIP
Unmatched condition detected *5
Event suppression detected *6
= SPOS01_F_QLT_SPP
BI board connection error detected*7
= SPOS01_F_BI_ERR
(510001 810101F59)
(510001 820101F5A)
IED serious error detected
SERI_ERR
Users must setup this condition correctly
(510001 0001011001)
Figure 4.1-29 Operate condition logic for ON/OFF in SPOS01
1
Note: “Command blocking” disables any operation except for itself; “Command
Blocking” is implemented as “CBK”in software switch controller (SOFTSW).The
IEC 61850 standard defines communication blocking as “CmdBlk”. For more
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......