6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1322 -
PWS alarm threshold setting
The IED has power supply module (PWS) at the far left slot. The user can confirm DC rated
voltage on the hardware nameplate by checking the cord at Positions ‘8’, but the user should
select either alarm thresholds for dropping DC voltage by inserting a jumper on the PWS
(Figure 13.5-1). See
Section Power supply module
in
Chapter Technical description
.
Ordering positions
7
8
9
A B
C D
E F
G H
J
K L
- x 1 - x x x - x x - x x - x x - x x x
DC rated voltage, e.g., 1=
’110 to 250Vdc’, selected by the ordering
Figure 13.5-1 Alarm threshold set on PWS module
CAUTION
Note: A short-wire is connected between terminal screws No. 35–37 ( No.35–36 for type
using the ring terminal). It is done by the manufacturer. The user shall remove
that when the user undertakes the dielectric voltage test for the IED; and the user
shall connect again the terminals with that after the test (See
Appendix: Notes for
the dielectric voltage test).
Type using compression terminals
Type using ring terminals
29
30
31
32
33
34
35
36
37
38
39
40
FG
Short wire
28
30
32
34
36
38
27
29
31
33
35
FG
Short wire
FG
Figure 13.5-2 PWS terminal labels
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......