6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1237 -
FUN
Function type (FUN) applied to a command response frame is set referring to Table 11.4-13.
The FUN can be set to 0 to 255. When clicking the “Change all FUNs” on the Common
setting screen, all FUNs are changed to the setting values at Common setting.
DCO/Sig Off Name, Signal Off Desc., DCO Signal On Name, Signal On Desc.,
Inverse
“Sig off” and “Sig On” are used to set the Data ID of control object in General command.
(Hereafter, these are described as “command output signal”.) “Inverse” is used to reverse
the logic when controlling the command output signal.
When the command output signal is treated as two signals (Sig Off
Sig On), the
control scheme is shown as the following table by the combination of the receiving command
DCO and Inverse setting.
For example, when the DCO=Off command is received under “Inverse” no-checked,
the command output signal of “Sig Off” is controlled to “1”. “Sig On” is not controlled.
Table 11.4-13
Control Scheme of Command Output Signal (Sig Off
Sig On)
“Inverse” checked
Control object
Receiving
command DCO
Checked
No-checked
Signal specified
to Sig.off
Signal specified
to Sig.on
Signal specified
to Sig.off
Signal specified to
Sig.on
Off
Controlled to “1” Not controlled Controlled to “0”
Not controlled
On
Not controlled Controlled to “1” Not controlled
Controlled to “0”
When the command output signal is treated as one signal (Sig Off
Sig On), the
control scheme is shown in Table 11.4-14. For example, when the DCO=On command is
received under “Inverse” checked, the command output signals of “Sig On” and “Sig Off” are
controlled to “0”. “Sig On” is not controlled.
Table 11.4-14
Control Scheme of Command Output Signal (Sig Off = Sig On)
“Inverse” checked
Control object
Receiving
command DCO
Checked
No-checked
Signal specified
to Sig.off
Signal specified
to Sig.on
Signal specified
to Sig.off
Signal specified
to Sig.on
Off
Controlled to “0”
Controlled to ”1”
On
Controlled to ”1”
Controlled to “0”
When setting the “Sig Off”, “Sig On” and “Inverse”, check the specifications of the
command output signals of communication and others, and then set them.
Valid time
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......