background image

 

E6581341 

 

 

 
 
 
 
 
 
 
 

 

Expansion IO Card Option 2 

 

ETB004Z Instruction manual 

 

 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

NOTICE 

 

1. Make sure that this instruction manual is delivered to the end user of the expansion 

IO card option. 

2. Read this manual before installing or operating the expansion IO card option. Keep 

it in a safe place for reference. 

3. All information contained in this manual are subject to change without notice. 

Please confirm the latest information on our web site “www.inverter.co.jp”. 

 

Summary of Contents for ETB004Z

Page 1: ...red to the end user of the expansion IO card option 2 Read this manual before installing or operating the expansion IO card option Keep it in a safe place for reference 3 All information contained in this manual are subject to change without notice Please confirm the latest information on our web site www inverter co jp ...

Page 2: ...may lead to injury 1 to people or that these errors may cause damage to physical property 2 1 Such things as injury burns or shock that will not require hospitalization or long periods of outpatient treatment 2 Physical property damage refers to wide ranging damage to assets and materials Meanings of symbols Marking Meaning of marking Indicates prohibition Don t do it What is prohibited will be de...

Page 3: ...rp portions such as leads of parts on the board the corner of board or etc on this option It may lead to injuries Caution Mandatory This option is an electrostatic discharge sensitive device Handle it where the environment is protected against electrostatic electricity Otherwise permanent damage to device will result Transportation installation Warning Prohibited Do not apply a dropping shock or o...

Page 4: ...tions or an accident Use an additional safety device with your VF AS1 PS1 or system to prevent a serious accident due to the unit malfunctions Usage without an additional safety device may cause an accident Disposal Caution Mandatory For safety s sake do not dispose of the disused inverter yourself but ask an industrial waste disposal agent If the collection transport and disposal of industrial wa...

Page 5: ...e unit Keep this manual near at hand of the operator who uses the Expansion IO option for future reference in the maintenance and inspection Type of expansion IO option card E T B 0 0 4 Z 0 Confirmation on accessories Following accessory parts are included in the expansion IO card option Upon unpacking confirm on the following parts Expansion IO card option unit 1 Instruction manual of expansion I...

Page 6: ...the inverter 7 2 2 Wiring 8 3 Functional description 10 3 1 Multi function output terminal 10 3 2 Multi function input terminal 11 3 3 10V power supply 11 3 4 Multi function analog output 12 3 5 Differential current input AI1 AI1 12 3 6 Analog input AI2 13 3 7 External thermal trip input TH2 TH2 13 3 8 Pulse train input RP 14 4 External diagram 15 5 Specification 16 6 Warranty 17 ...

Page 7: ... MON1 Multifunction programmable analog output 1 T B 2 MON2 Multifunction programmable analog output 2 P24 PLC Common terminal of extension terminal input LI5 Extension terminal input LI5 LI6 Extension terminal input LI6 LI7 Extension terminal input LI7 LI8 Extension terminal input LI8 T B 3 CC Digital signal equipotential 0V TH2 PTC input terminal TH2 PTC input terminal RP Pulse train input termi...

Page 8: ...n and remove the front panel cover b Install the option in the inverter by fitting the tabs on the lower side of the option into the slots at the lower part of the inverter front panel c Make sure the option is securely attached to the inverter Then check whether the plastic bosses on the inverter case have fitted in the holes at the upper and lower parts of the option d Insert the tabs at the low...

Page 9: ...LI7 LI8 Contact point input Changeover of sink or source No voltage contact input 24Vdc 5mA Sink input common voltage 24V ON less than 10Vdc OFF 16Vdc or more Source input ON 11Vdc or more OFF less than 5Vdc Note Even when an external power supply is used in sink logic mode i e when SINK PLC is selected connect the reference potential side 0V side cable from the power supply to the CC terminal 24V...

Page 10: ...nput output Digital signal equipotential 0V terminal for the control circuit AI1 AI1 Differential current input Current input Equal or under 20mA Voltage Differential input voltage under 5V Input voltage from 10V to 10V AI1 OP AI1 242Ω AI2 CCA Analog input Current input Equal or under 20mA Voltage input 0 to 10V AI2 15k ohm CCA 242 16 2k ohm MON1 MON2 Monitor output Multifunction programmable anal...

Page 11: ...nverter instruction manual Parameter Title Function Adjustment range Default setting f136 Output terminal function selection 7 OUT5 0 255 254 Always OFF f137 Output terminal function selection 8 OUT6 0 255 254 Always OFF f138 Output terminal function selection 9 R2 0 255 254 Always OFF Monitor Refer to the description on status monitor mode of inverter s instruction manual The output terminal stat...

Page 12: ... status monitor mode of inverter s instruction manual The input terminal status can be monitored by the input terminal status parameter fe06 and the parameter can be monitor by the serial communication fe06 bit No 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Symbol LI8 LI7 LI6 LI5 LI4 LI3 LI2 LI1 S4 S3 S2 S1 RES ST R F Note The LI1 LI4 are the terminal function of the expansion IO card option 1 3 3 10V p...

Page 13: ... output 1 Voltage 0 10V output 2 Current 0 20mA output 1 f692 MON2 output gradient characteristic 0 Negative inclination downward slope Note1 1 Positive inclination upward slope 1 f693 MON2 bias adjustment 10 0 100 0 0 0 Note1 When MON1 MON2 setting is the voltage 10 10V output f689 f689 setting is invalid and the MON1 MON2 gradient characteristics becomes the positive inclination 3 5 Differential...

Page 14: ...nalog AI2 optional circuit board voltage current switching 0 Voltage 1 Current 0 f228 AI2 input point 1 setting 0 100 0 f229 AI2 input point 1 frequency 0 0 fh Hz 0 0 f230 AI2 input point 1 setting 0 100 100 f231 AI2 input point 1 frequency 0 0 fh Hz 60 or 50 f478 Optional AI2 input bias 0 255 f479 Optional AI2 input gain 0 255 3 7 External thermal trip input TH2 TH2 By connecting the thermistor t...

Page 15: ...P high speed pulse input point 1 setting 100 100 0 f235 RP high speed pulse input point 1 frequency 0 0 fh Hz 0 0 f236 RP high speed pulse input point 2 setting 0 100 100 f237 RP high speed pulse input point 2 frequency 0 0 fh Hz 60 0 f378 Number of RP terminal input 12 9999 500 f660 Override additional input selection 0 12 11 RP pulse input 0 TH2 TH2 PTC thermistor Expansion IO card option P5 3k ...

Page 16: ... of option unit mm Dimension of optional unit The control panel depth increases about 21 6mm when the option is installed Secure the front space from the inverter control panel fully The space which is necessary for the option installation varies in the inverter capacity rate Please refer to the inverter instruction manual ...

Page 17: ...11Vdc or more OFF less than 5Vdc 24V power supply DC24V 60mA External thermal trip input 1 circuit The detection level is below Tripping value about 50 ohm or less or about 3k ohm or more Reset value about 1 8k ohm 10V power supply DC 10V 10mA Open collector output Multi function programmable output 2 circuit Current 50mA max with external power supply 20mA max with internal power supply Voltage m...

Page 18: ...tment service will be charged for the following cases 1 Fault or damage resulting from misuse unauthorized modification or repair 2 Fault or damage resulting from falling down of the product or traffic accident during transportation 3 Fault or damage originating from fire salt water salty breezes some kind of gas earthquake storm or flood lightning abnormal supply voltage other natural disasters 4...

Reviews: