3.4 External thermal trip input (TH1+, TH1-) 

By connecting the thermistor to TH1+ and TH1- terminal, when the thermistor value is 
unusual, the inverter can be trip.

   

 

The resistor value   

between TH1+ and TH1- 

Detect condition 

Movement 

about under 70 ohm 

Thermistor short broken detection 

oh2

 trip 

about 70 - about 2.5k ohm 

Normal value 

―――

 

about 1.6k ohm 

Thermistor fault reset 

―――

 

about 3k ohm 

Thermistor fault detection 

oh2

 trip 

 

Parameter 

Title   

Function 

Adjustment range 

Default setting 

f637

PTC thermal selection 

0: Deselect 
1: Select 

 

 

 

TH1+

TH1-

PTC
thermistor

Expansion IO card option

P15

4.2k

Voltage

detection

circuit

Summary of Contents for ETB003Z

Page 1: ...n a Toshiba Schneider Inverter Corporation 2005 All rights reserved NOTICE 1 Make sure that this instruction manual is delivered to the end user of the expansion IO card option 2 Read this manual before installing or operating the expansion IO card option Keep it in a safe place for reference 3 All information contained in this manual are subject to change without notice Please confirm the latest ...

Page 2: ...n may lead to injury 1 to people or that these errors may cause damage to physical property 2 1 Such things as injury burns or shock that will not require hospitalization or long periods of outpatient treatment 2 Physical property damage refers to wide ranging damage to assets and materials Meanings of symbols Marking Meaning of marking Indicates prohibition Don t do it What is prohibited will be ...

Page 3: ...p portions such as leads of parts on the board the corner of board or etc on this option It may lead to injuries Caution Mandatory This option is an electrostatic discharge sensitive device Handle it where the environment is protected against electrostatic electricity Otherwise permanent damage to device will result Transportation installation Warning Prohibited Do not apply a dropping shock or ot...

Page 4: ...tions or an accident Use an additional safety device with your VF AS1 PS1 or system to prevent a serious accident due to the unit malfunctions Usage without an additional safety device may cause an accident Disposal Caution Mandatory For safety s sake do not dispose of the disused inverter yourself but ask an industrial waste disposal agent If the collection transport and disposal of industrial wa...

Page 5: ...nit Keep this manual near at hand of the operator who uses the Expansion IO card option for future reference in the maintenance and inspection Type of expansion IO option card E T B 0 0 3 Z 0 Confirmation on accessories Following accessory parts are included in the expansion IO card option Upon unpacking confirm on the following parts Expansion IO card option unit 1 Instruction manual of expansion...

Page 6: ...talling the IO card option in the VF AS1 PS1 7 2 1 Connection to the inverter 7 2 2 Wiring 8 3 Functional description 10 3 1 Multi function output terminal 10 3 2 Multi function input terminal 11 3 3 10V power supply 11 3 4 External thermal trip input TH1 TH1 12 4 External diagram 13 5 Specification 14 6 Warranty 15 ...

Page 7: ...tput 10V P24 PLC Common terminal of extension terminal input LI1 Extension terminal input LI1 LI2 Extension terminal input LI2 LI3 Extension terminal input LI3 LI4 Extension terminal input LI4 T B 2 CC Digital signal equipotential 0V TH1 PTC input terminal TH1 PTC input terminal OUT3 Extension terminal output OUT3 OUT4 Extension terminal output OUT4 NO1 Output 3 and 4 common terminal T B 3 CC Digi...

Page 8: ...own and remove the front panel cover b Install the option in the inverter by fitting the tabs on the lower side of the option into the slots at the lower part of the inverter front panel c Make sure the option is securely attached to the inverter Then check whether the plastic bosses on the inverter case have fitted in the holes at the upper and lower parts of the option d Insert the tabs at the l...

Page 9: ...LI3 LI4 Contact point input Changeover of sink or source No voltage contact input 24Vdc 5mA Sink input common voltage 24V ON less than 10Vdc OFF 16Vdc or more Source input ON 11Vdc or more OFF less than 5Vdc Note Even when an external power supply is used in sink logic mode i e when SINK PLC is selected connect the reference potential side 0V side cable from the power supply to the CC terminal 24V...

Page 10: ... Voltage detection circuit 3k ohm TH1 P5 TH1 N10 10V power upply DC 10V 10mA N10 OP 100 ohm OUT3 OUT4 NO1 Multifunction programmable open collector output Open collector output Drive current External power supply used 50mA Internal power supply used 20mA Drive voltage 12V min 30V max Isolated other circuit 20 ohm OUT3 OUT4 20 ohm NO1 CC Common to input output Digital signal equipotential 0V ermina...

Page 11: ...rter instruction manual Parameter Title Function Adjustment range Default setting f133 Output terminal function selection 4 OUT3 0 255 254 Always OFF f134 Output terminal function selection 5 OUT4 0 255 254 Always OFF f135 Output terminal function selection 6 R1 0 255 254 Always OFF Monitor Refer to the description on status monitor mode of inverter s instruction manual The output terminal status ...

Page 12: ...atus monitor mode of inverter s instruction manual The input terminal status can be monitored by the input terminal status parameter fe06 and the parameter can be monitor by the serial communication fe06 bit No 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Symbol LI8 LI7 LI6 LI5 LI4 LI3 LI2 LI1 S4 S3 S2 S1 RES ST R F Note The LI5 LI8 are the terminal function of the expansion IO card option 2 3 3 10V powe...

Page 13: ...H1 Detect condition Movement about under 70 ohm Thermistor short broken detection oh2 trip about 70 about 2 5k ohm Normal value about 1 6k ohm Thermistor fault reset about 3k ohm Thermistor fault detection oh2 trip Parameter Title Function Adjustment range Default setting f637 PTC thermal selection 0 Deselect 1 Select 0 TH1 TH1 PTC thermistor Expansion IO card option P15 4 2k Voltage detection cir...

Page 14: ... of option unit mm Dimension of optional unit The control panel depth increases about 21 6mm when the option is installed Secure the front space from the inverter control panel fully The space which is necessary for the option installation varies in the inverter capacity rate Please refer to the inverter instruction manual ...

Page 15: ... output 1 circuits for output of 1C contact point 250Vac 2A cosφ 1 250Vac 1A cosφ 0 4 30Vdc 1A Contact point input Changeover of sink source Multi function programmable input 4 contact inputs Sink input 24V common voltage ON less than 10Vdc OFF 16Vdc or more Source input ON 11Vdc or more OFF less than 5Vdc 24V power supply DC24V 60mA External thermal trip input 1 circuit The detection level is bel...

Page 16: ...tment service will be charged for the following cases 1 Fault or damage resulting from misuse unauthorized modification or repair 2 Fault or damage resulting from falling down of the product or traffic accident during transportation 3 Fault or damage originating from fire salt water salty breezes some kind of gas earthquake storm or flood lightning abnormal supply voltage other natural disasters 4...

Reviews: