E6580772
③
13
Parameter name
Title
Setting value
Details
Com. Error
selection
f850
0
to
4
Sets the inverter operation at time of communication error.
The action of inverter will be different depending on the
status (during operation or halt) of the inverter. (Note 2)
0
: During halt
Inverter stops after free run.
During operation
Inverter trips.
1
: During halt
Inverter stops after free run.
During operation
Inverter stops after free run.
2
: Invalid
(Setting is enabled with F10M
option connected.)
3
: During halt
Inverter decelerates to stop.
During operation
Inverter decelerates to stop.
4
: During halt
Inverter continues to run.
During operation
Inverter continues to run.
Com. Error
detecting time
f851
0
to
1000
Sets the time until the communication error is detected.
Setting is done by a unit of ms. (Note 3)
Reset function
f899
0
,
1
Resets the inverter station.
0
: No action
1
: To reset the inverter station. After resetting, setting
data returns to
0
.
(Note 1) For setting the parameters, never duplicate the station address on the same communication line.
PLC rink relay register is automatically allocated according to the setting of the station address. As for the
setting of station addresses, consider the allocation of rink relay register that is determined by the other
station addresses and the number of words that have been set in the parameters
f831
to
f836
, and
f841
to
f846
.
The maximum setting value for station address is 255, however when 255 is set, only one word of scan
data can be set. To set the scan data in its maximum value of 12 words, setting value of the station
address should be: 255-(12-1)= 244.
(Note 2) Setting of “free-run stop” is valid when the “operation command mode selection” [
cmod
] is
selected to the optional add-on cassette.
Setting of “deceleration stop” is valid when the “operation command mode selection” [
cmod
] is selected
to the optional add-on cassette or when the “speed setting mode selection” [
fmod
] is selected to the
optional add-on cassette. At the same time the deceleration stop returns the command of run/stop and the
speed reference value to 0. Except when the above command setting is selected, inverter cannot be
stopped.
Furthermore when the “operation command mode selection” [
cmod
] is set to other than the optional
add-on cassette and when the “speed setting mode selection” [
fmod
] is selected to the optional add-on
cassette, in some cases inverter can not stop running because of the setting of the parameters (zero-
speed operation setting). Torque control is valid when the “operation command mode selection” [
cmod
]
is set to the optional add-on cassette, but the inverter operation becomes “free-run stop” at that time.