Direct Access Parameter Information
Note: NO/NC = Normally Opened/Normally Closed contact. NO/NC selection numbers are used when
making system changes via communications.
102 103
Commercial Power/ASD Switching
— Initiates the ASD-to-Commercial Power switching
function. See
for additional information on this feature.
104 105
Frequency Command Priority Switching
— Toggles frequency control to and from the set
-
tings of
.
106 107
V/I Terminal Priority
— Assigns Speed control to the V/I Terminal and overrides the
setting.
108 109
Command Terminal Board Priority
— Assigns
Command
control to the Terminal Board and
overrides the
setting.
110 111
Parameter Edit Enable
— Allows for the override of the lock out parameter setting (F700)
allowing for parameter editing (SELECTION NOT USED WITH THE Q9 Plus ASD).
122 123
Fastest Deceleration Command
— Using dynamic braking (if enabled and supported), stops
the motor at the fastest rate allowed by the load.
124 125
Preliminary Excitation
— Applies an excitation current to the motor (holds shaft stationary)
for the duration of the activation.
136 137
Start-Stop HOA
— Activates the Auto Start-Stop operating mode in accordance with the set
-
tings of
138 139
Low Suction/No Flow Protection
— Will not allow the ASD to start if activated, or terminates
the ASD output upon activation (if running) in the event of the loss of feed water or a closed
output valve at the pump output.
140 141
Sealing Water
— Once an adequate water supply is detected at the pump seal via a reed
switch, activation enables the ASD for normal operations.
142 143
Virtual Linear Pump Enable/Disable Switch
— Activation enables the Virtual Linear Pump
function for normal operation. The Virtual Linear Pump function is disabled when the terminal
is not active.
144 145
TBA ON Float
— Activation runs the ASD at the setting of
146 147
TBA OFF Float
— Activation has a dual function:
1) Changes the operating mode from Process Hold to Direct.
2) Turns off the ASD.
148 149
TBA Trigger Float
— Activation changes the operating mode from Process Hold to Direct.
150 151
TBA Warning Float
— This input is typically connected to a float switch that, when activated,
annunciates that the fluid level is now critical. The discrete output terminals OUT1 and/or
OUT2 may be associated with the activation (set OUT1/OUT2 to TBA Alarm Float to activate
an auxiliary system — i.e., aux pump, relief valve, audible/visual alarm, etc.).
152 153
TBA Local-Off-Auto
— Activation enables Time-Based Alternation operation. Operates in
conjunction with the setting of
.
154 155
V/Hz Rate Switching
— This function is not used with the Q9 Plus ASD.
156 157
Manual Boost Switching
— Activation applies the torque boost setting of
to
motor profiles 1 and 2, respectively, for the duration of the activation.
Table 9. Discrete Input Terminal Assignment Selections and Descriptions. (Cont)
Sel. No.
Terminal Selection Descriptions
NO NC
Sealing
Water
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......