Direct Access Parameter Information
Virtual Linear Pump Start/Stop Mode
Program
Virtual Linear Pump
Start and Stop Points
During a properly configured Virtual Linear Pump operation, this
parameter Enables/Disables the ability of the system to receive
transducer input to manage system starts and stops as it per
-
tains to the process variable.
This parameter is also used to select the ASD response (Stop or
Start) upon meeting the criteria of
and
On Forward = Run ASD while measured signal is
setting.
On Reverse = Run ASD while measured signal is
setting.
Settings:
0 — Off
1 — On (Forward Acting)
2 — On (Reverse Acting)
Direct Access Number —
F385
Parameter Type —
Selection List
Factory Default —
Off
Changeable During Run —
Yes
Virtual Linear Pump Start-Stop Delay Timer
Program
Virtual Linear Pump
Start and Stop Points
During a properly configured Virtual Linear Pump operation, this
parameter establishes the time that the Start-Stop criteria of
must be maintained to activate the Auto Start-
Stop function.
This feature is used to minimize system responses to rapid fluctu
-
ations in the feedback signal.
for additional information on this parameter.
Direct Access Number —
F387
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6553.5
Units — Seconds
WARNING
The Auto Start-Stop operating mode may result in the unex
-
pected Start or Stop of the motor. Signs to this effect are to be
posted at the location of the motor/pump.
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......