Direct Access Parameter Information
https://www.toshiba.com/tic/
227
Communications Option Station Address Monitor
Program
Communications
Communication Options
This parameter is used in the setup of the communications net
-
work by reading the Media Access Code (MAC) address of the
ASD that is connected to a node of the communications system.
The MAC Address is set via DIP switches of the optional device.
See the DeviceNet Option Instruction Manual (P/N 58683) for
additional information on this parameter.
Direct Access Number —
F853
Parameter Type —
Selection List
Factory Default —
0 (Disabled)
Changeable During Run —
Yes
Minimum — 0
Maximum — 127
Communications Option Speed Switch Monitor DeviceNet/
CC-Link
Program
Communications
Communication Options
This parameter is used in the setup of the communications net
-
work by reading the hardware-specific settings of the option card
being used with the ASD.
If using the DEV002Z
Devicenet card, this parameter reads the
hardware switch SW300 setting of the Devicenet card. SW300
sets the baud rate and the MAC address of the option card that is
connected to a node of the communications system.
See the DeviceNet Option Instruction Manual (P/N 58683) for
additional information on this parameter or see the instruction
manual for the option being used with the Q9 Plus ASD.
Direct Access Number —
F854
Parameter Type —
Hardware
Selectable
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Free Notes
Program
Communications
Communication Settings
This is an unused parameter that has allocated memory space.
The space may be used at the discretion of the user. This space
may be used to store information or a note to be transferred using
communications.
Direct Access Number —
F880
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 65535
Network Option Reset Setting
Program
Communications
Communication Settings
This parameter plays a role in the setup of the communications
network by establishing the targets of a Reset command received
via the communications link.
Settings:
0 — ---
1 — Reset Option Board and ASD
Direct Access Number —
F899
Parameter Type —
Selection List
Factory Default —
- - -
Changeable During Run —
No
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...