206
https://www.toshiba.com/tic/
Direct Access Parameter Information
Free Unit
Program
Utilities
Display Parameters
This parameter is used in conjunction with
method in which the frequency is displayed on the EOI.
The multiplier setting of
will be applied to the display of all
frequencies if all frequencies are selected at this parameter.
,
, and
ONLY if PID Process Data
is selected at
this parameter.
Settings:
0 — All Frequencies
1 — PID Process Data
Direct Access Number —
F703
Parameter Type —
Selection List
Factory Default —
All Frequen
-
cies
Changeable During Run —
Yes
Free Unit Display Gradient Characteristic
Program
Utilities
Display Parameters
The ASD-displayed response to output speed changes will be
displayed as directly proportional or inversely proportional as a
function of this parameter setting.
Selecting Negative Gradient displays an increased output speed
as going more negative.
Selecting Positive Gradient displays an increased output speed
as going more positive.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number —
F705
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
Free Unit Display Bias
Program
Utilities
Display Parameters
In conjunction with the setting of
, this parameter sets the
bias of the EOI speed display.
The frequency entered here will be multiplied by the setting of
and then displayed as the zero value on the EOI display.
Direct Access Number —
F706
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq.
Units — Hz
Change Step Selection 1
Program
Utilities
Display Parameters
In conjunction with the parameter setting of
F708, t
his parameter
sets the amount that the output speed will increase or decrease
for each speed command change entered from the EOI using the
Rotary Encoder.
Direct Access Number —
F707
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq.
Units — Hz
Summary of Contents for DN-68249-003