Direct Access Parameter Information
Forced Fire-Speed Control
Program
Protection
Fire-Speed Control
This parameter is used to enable the Forced Fire Speed func
-
tion. The Forced Fire Speed function runs
must be configured to
use the Forced Fire Speed function.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number —
F650
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Under-Torque Detection
Program
Protection
Under-Torque Detection
This parameter sets the ASD operating mode and disposition in
the event that an Under-Torque condition were to occur.
For an Under-Torque event to occur, the minimum criteria of
parameters
must be met:
Settings:
0 — Alarm Mode
1 — Trip Mode
Direct Access Number —
F651
Parameter Type —
Selection List
Factory Default —
Alarm Mode
Changeable During Run —
Yes