Direct Access Parameter Information
https://www.toshiba.com/tic/
193
Brake Equipped Motor Restart Condition
Program
Special
Special Parameters
This parameter is used with synchronous motor applications only
and is not used with the Q9 Plus ASD.
Settings:
0 — No Wait Time for Frequencies Less Than 10 Hz
1 — No Wait Time for Frequencies Less Than 20 Hz
Direct Access Number —
F643
Parameter Type —
Selection List
Factory Default —
No Wait Time
for Frequencies Less Than 10
Hz
Changeable During Run —
No
Select Operation When V/I is Disconnected
Program
Terminal
Input Special Functions
This parameter is used to select a system disposition in the event
of the loss of the V/I input signal.
The system will either trip, run the speed set at
,
setting in the Direct
mode.
Note:
must be configured to use the preset
speed selection.
Settings:
0 — Trip
1 — Preset Speed 14
2 — Direct Mode Setpoint
Direct Access Number —
F644
Parameter Type —
Selection List
Factory Default —
Trip
Changeable During Run —
No
PTC Thermal Mode
Program
Special
Special Parameters
This parameter sets the ASD disposition in the event that the
PTC resistance exceeds the setting of parameter
The RR input terminal becomes the PTC Thermal Input terminal
when Alarm or Trip is selected at this parameter.
This parameter setting overrides the Frequency Mode 1 and Fre
-
quency Mode 2 settings.
Settings:
0 — Disable
1 — Enable (trip mode)
2 — Enable (alarm mode)
Direct Access Number —
F645
Parameter Type —
Selection List
Factory Default —
Disable
Changeable During Run —
No
PTC Detection Resister Value
Program
Special
Special Parameters
This parameter provides a user-set resistance threshold for the
thermal sensor that, once exceeded, will activate the selection of
.
Direct Access Number —
F646
Parameter Type —
Numerical
Factory Default —
3000
Changeable During Run —
Yes
Minimum — 100
Maximum — 9999
Units —
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......