Direct Access Parameter Information
https://www.toshiba.com/tic/
191
Annual Average Ambient Temperature
Program
Special
Special Parameters
This parameter is used in conjunction with a discrete output ter
-
minal setting to notify the operator of the remaining useful life of
critical components of the ASD system.
With a discrete output terminal set to Part Replacement Alarm
(see
) and the calculation derived from the
parameter setting, maintenance scheduling may be enhanced.
Settings:
1 — Under 10° C (50° F)
2 — Under 20° C (68° F)
3 — Under 30° C (86° F)
4 — Under 40° C (104° F)
5 — Under 50° C (122° F)
6 — Under 60° C (140° F)
Direct Access Number —
F634
Parameter Type —
Selection List
Factory Default —
Under 30°
Changeable During Run —
Yes
Rush Current Suppression Relay Activation Time
Program
Special
Special Parameters
At system start up, this parameter sets a time-delay for the start
of the Rush Relay activation in an attempt to allow the DC bus
voltage to reach the normal operating level before outputting a
signal to the motor.
Direct Access Number —
F635
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 2.5
Units — Seconds
PTC 1 Thermal Selection
Program
Special
Special Parameters
This parameter Enables/Disables the optional external thermal
detection circuit of the Expansion IO Card Option 1. A thermistor
is connected from TH1+ to TH1- of TB3 on the Expansion IO
Card Option 1.
Should the thermistor resistance reading fall below 50W because
of an over-temperature condition or exceed 3000W because of
an open circuit, an External Thermal Fault (OH2) will be incurred.
Note: While this parameter is Enabled, the system cannot be
restarted until the thermistor value recovers to the level of
1.8
k
from an over-temperature condition. An Auto-
Restart will not be initiated subsequent to an External
Thermal Trip (OH2); a manual restart will be required.
Settings:
0 — Disabled
1 — Detect Disconnect
Direct Access Number —
F637
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......