Direct Access Parameter Information
https://www.toshiba.com/tic/
105
V/I Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input
terminal when the V/I terminal is used as the control input while
operating in the Speed Control
mode.
This parameter sets V/I Input Point 1 Frequency and is the fre
-
quency that is associated with the setting of
V/I Input Point 1 Set
-
ting
when operating in the Speed Control
mode.
See V/I Input Point 1 Setting
) for additional information on
this parameter.
Direct Access Number —
F202
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq.
(
Units — Hz
V/I Input Point 2 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input
terminal when the V/I terminal is used as the control input while
operating in the Speed Control mode or the Torque Control
mode.
This parameter sets the V/I input level that is associated with V/I
Input Point 2 Frequency
when operating in the Speed control
mode or is associated with the V/I Input Point 1 Rate when oper
-
ating in the Torque Control mode.
This value is entered as 0% to 100% of the V/I input signal range.
See V/I Input Point 1 Setting (
) for additional information on
this parameter when used for Speed control.
See V/I Input Point 1 Rate (
) for additional information on
this parameter when used for Torque Control.
Direct Access Number —
F203
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
V/I Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input
terminal when the V/I terminal is used as the control input while
operating in the Speed Control mode.
This parameter sets V/I Input Point 2 Frequency and is the fre
-
quency that is associated with the setting of V/I Input Point 2 Set
-
ting when operating in the Speed Control mode.
See V/I Input Point 1 Setting (
) for additional information on
this parameter.
Direct Access Number —
F204
Parameter Type —
Numerical
Factory Default —
(ASD-Depen
-
dent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq.
(
Units — Hz
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......