MODE SETTING FOR THE CONTROLLER
Operation mode
Use SW1-<6> for the operation mode setting.
Control group selection
Either simultaneous mode or an arbitrary range of a line and 16 groups (1 to 16, 17 to 32, 33 to 48, and 49 to 64)
can be selectively set.
* When the control group selection is used, only the set group range is displayed.
* The control group selection is available only for one line.
OFF side: Central control mode
This Compliant Manager is used as a central control unit.
Settings with the remote controller are inhibited by the setting of the Compliant Manager.
ON side:
Remote control mode
This Compliant Manager is used as a remote controller.
Settings with the Compliant Manager are inhibited by the setting of another central control unit.
DIP-SW1
DIP-SW2
<2>
<3>
<4>
<5>
<5>
<6>
All groups
OFF
OFF
OFF
OFF
OFF
OFF
LINE 1
Group 1 to 16
ON
OFF
OFF
OFF
OFF
ON
Group 17 to 32
OFF
ON
OFF
OFF
OFF
ON
Group 33 to 48
OFF
OFF
ON
OFF
OFF
ON
Group 49 to 64
OFF
OFF
OFF
ON
OFF
ON
LINE 2
Group 1 to 16
ON
OFF
OFF
OFF
ON
ON
Group 17 to 32
OFF
ON
OFF
OFF
ON
ON
Group 33 to 48
OFF
OFF
ON
OFF
ON
ON
Group 49 to 64
OFF
OFF
OFF
ON
ON
ON
Example:
When setting LINE 1 (group 1 to 32) in
the control group selection
ON
ON
OFF
OFF
OFF
ON