MB Interface

Installation Manual

Configuration through micro switches

S1 - Hydro unit type selection

S3 - Modbus slave address and baudrate

 * Default value

S4 - Degrees/Decidegrees (x10), temperature magnitude (ºC) and RS-485 termination resistor 

 * Only in the interfaces conected at both ends of the bus must be activated the termination resistor, not in the rest. The RS-485 bus can be biased through internal 

jumpers JP2 and JP3. Consult the user manual for details. 

WEEE Document
http://www.toshiba-carrier.co.jp/global/products/network/index.htm

Switches

 1  2  3  4 

Description

  x  x  x

Hydro unit type. Advanced functionalities for Estia Hydro unit 5 series units. Please, check the user manual for more information. (default and 
recommended value) 

  

  x  x

Hydro unit type. Advanced functionalities for Estia Hydro unit 4 series units. Please, check the user manual for more information. 

  

  x  x

Reserve.

  

  x  x

Reserve.

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

0

  

  

  

  

  

8

  

  

  

  

  

16

  

  

  

  

  

24

  

  

  

  

  

32

  

  

  

  

  

40

  

  

  

  

  

48

  

  

  

  

  

56

  

  

  

  

  

1*

  

  

  

  

  

9

  

  

  

  

  

17

  

  

  

  

  

25

  

  

  

  

  

33

  

  

  

  

  

41

  

  

  

  

  

49

  

  

  

  

  

57

  

  

  

  

  

2

  

  

  

  

  

10

  

  

  

  

  

18

  

  

  

  

  

26

  

  

  

  

  

34

  

  

  

  

  

42

  

  

  

  

  

50

  

  

  

  

  

58

  

  

  

  

  

3

  

  

  

  

  

11

  

  

  

  

  

19

  

  

  

  

  

27

  

  

  

  

  

35

  

  

  

  

  

43

  

  

  

  

  

51

  

  

  

  

  

59

  

  

  

  

  

4

  

  

  

  

  

12

  

  

  

  

  

20

  

  

  

  

  

28

  

  

  

  

  

36

  

  

  

  

  

44

  

  

  

  

  

52

  

 

  

  

  

60

  

  

  

  

  

5

  

  

  

  

  

13

  

  

  

  

  

21

  

  

  

  

  

29

  

  

  

  

  

37

  

  

  

  

  

45

  

  

  

  

  

53

  

  

  

  

  

61

  

  

  

  

  

6

  

  

  

  

  

14

  

  

  

  

  

22

  

  

  

  

  

30

  

  

  

  

  

38

  

  

  

  

  

46

  

  

  

  

  

54

  

  

  

  

  

62

  

  

  

  

  

7

  

  

  

  

  

15

  

  

  

  

  

23

  

  

  

  

  

31

  

  

  

  

  

39

  

  

  

  

  

47

  

  

  

  

  

55

  

  

  

  

  

63

  

  

  

  

  

Switches

 7  8

Description

  

 2400bps 

  

 4800bps 

  

 9600bps (default value) 

  

 19200bps 

Switches

 1  2  3  4 

Description

  x  x  x

Temperature values in Modbus register are represented in degrees (x1) (default value) 

  x  x  x

Temperature values in Modbus register are represented in decidegrees (x10) 

x  x  x  

RS-485 bus without termination resistor (default value) 

x  x  x  

Internal termination resistor of 120

 connected to RS-485 bus * 

TOSHIBA

BMS-IFMB0AWR-E

RS-485

A+

A B

B-

L1 L2 S1

S4

S3

ON 1 2 3 4 

S4

ON  1 2 3 4 5 6 7 8 

S3

 

ON 1 2 3 4 

S1

 

L1 (green)

L2 (red)

Hydro unit type selection. It is recommended not to change the default value 
unless you are sure about the Hydro unit type you own. 

Normal operation: At device start-up, both LEDs are on during 5 seconds. 
Afterwards only the green LED remains flashing (1900ms Off/100ms On). For 
any other indication, consult the User Manual.

Modbus slave address and Baudrate 
configuration. 

Configuration degrees/decidegrees (x10), 
temperature magnitude (ºC) and RS-  485 
termination resistor. 