MB Interface

Installation Manual

2

-EN

Safety instructions

 WARNING

Follow carefully these safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the interface 
and/or the Hydro unit. 
• This interface must be installed by accredited technical personnel (electrician, installer, or technical personnel) and following all the safety instructions. 
• Before manipulating the Hydro unit, be sure it is completely disconnected from Mains power. 
• Do not modify the unit. (A fire or an electric shock may occur)
• This interface must only be installed in a restricted access location by user. 
• Do not install the unit in any of the following places. 

• Humid or wet place 
• Dusty place 
• Place exposed to direct sunlight 
• Place where there is a TV set or radio within one meter 
• Place exposed to rain (outdoors, under eaves, etc.) 

• Use predefined cable and connect them certainly. Keep the connecting terminal free from external force. 

It may cause an exothermic or a fire. 

• Strip the insulation from the cable that connects to the connector (RS-485 and A B bus) following the dimensions shown in the diagram below. 
• When connecting the cable to the connector (RS-485 and A B bus), ensure the core wires do not protrude from the connector. 
• Use two-core cabtyre cable. 

Installation instructions

• Disconnect the Hydro unit from Mains Power. 
• Fix the interface beside the Hydro unit (wall mounting) following the instructions in the diagram below or install it inside the Hydro unit (respect the safety 

instructions given above). 

• Connect the interface to A B bus in any point of the bus. The A B bus is the bus that connects the Hydro unit and the wired remote controller, is a two-wire bus 

connecting terminals A B of both, this A B connection has no specific polarity. 

• Connect the RS-485 bus to the connector RS-485 of the interface. 
• Close the Hydro unit and reconnect it to Mains Power. 

• Follow the instructions on the user manual for configuring and commissioning the interface. 
• Follow the instructions of the next page to configure the interface through on-board DIP-switches. 

IMPORTANT: 

•  Use only one remote controller. A sub-remote controller cannot be connected when connecting this interface. 
• It is not possible to mix and connect Hydro unit 4 series and 5 series. 

NOTE

The cable used for connection of BMS-IFMB0AWR-E to A B bus can be any two-core cabtyre cable, the maximum distance for bus A B is 50 meters, consult the 
manual of the Hydro unit for more details. 
Respect the maximum distance of 500 meters for the bus, no loop or star topologies are allowed for RS-485 bus, a terminator resistor of 120 

 must be present at 

each end of the bus to avoid signal reflections and also a fail-safe biasing mechanism.

NOTE

In its place there is a pair of cables to connect the Remote Controller. Use these cables to connect the AB bus. Check your Hydro unit user or service manual for 
more information. 

TOSHIBA

BMS-IFMB0AWR-E

RS-485

A+

A

A

TB07

B

B

B-

53 mm

90 mm

(20 mm)

(5 mm)

Hydro Unit

The terminal 
block in the 
hydro unit. 

Connection to A B bus.

Two-core cabtyre cable.

Max. 50 m

MODBUS RTU
RS-485 
Bus

Interface installation
• Install the 

interface on the 
DIN rail.

• For  wall  mount 

extract the upper 
and down staples 
until you hear the 
“click”.

Length of stripped RS-485 and A B bus communication 
cable

DIN rail

Reviews: