D.7 – Input Transformer Current for Given Input Voltage
TABLE D.7 – INPUT TRANSFORMER CURRENT FOR GIVEN INPUT VOLTAGE
Input
Voltage
Input Current (Input Cu Charging Current) at Full Load (A)
15 kVA
20 kVA
25 kVA
30 kVA
50 kVA
80 kVA
208/120V
42 (46)
55 (60)
69 (74)
83 (88)
139 (148)
222 (238)
220/127V
41 (45)
54 (59)
68 (72)
81 (86)
136 (144)
217 (232)
230/133V
39 (43)
52 (56)
65 (69)
78 (82)
130 (138)
207 (222)
240/139V
37 (41)
50 (54)
62 (66)
75 (79)
124 (132)
199 (213)
380/220V
24 (26)
31 (34)
39 (42)
47 (50)
78 (84)
126 (134)
400/227V
22 (25)
30 (32)
37 (39)
45 (47)
75 (79)
119 (128)
415/240V
22 (24)
29 (31)
36 (38)
43 (46)
72 (77)
115 (123)
480/277V
19 (21)
25 (27)
31 (33A
37 (39)
62 (66)
99 (106)
600/347V
15 (17)
20 (22)
25 (27)
30 (32)
50 (53)
80 (85)
D.8 – Output Transformer Current for Given Output Voltage
TABLE D.8 – OUTPUT TRANSFORMER CURRENT AT GIVEN OUTPUT VOLTAGE
Output
Voltage
Output Current at Full Load (A)
15 kVA
20 kVA
25 kVA
30 kVA
50 kVA
80 kVA
208/120V
42
56
69
83
139
222
220/127V
39
52
66
79
131
210
230/133V
38
50
63
75
126
201
240/139V
36
48
60
72
120
192
380/220V
23
30
38
46
76
122
400/227V
22
29
36
43
72
115
415/240V
21
28
35
42
70
111
480/277V
18
24
30
36
60
96
600/347V
14
19
24
29
48
77