TOSHIBA
5.2 4200FA 15/25 kVA w/Internal Transformer
Model
Number
C42#3*150#AMXN
C42#3*250#AMXN
Input
# =
(B: 208; H: 220; C: 240; N: 380–415
Δ
-wye; P: 380–415 wye; D: 480;
M: 600) VAC
Output
*=
(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye: M:600) VAC
Rated Output Capacity
15 kVA
25 kVA
External
Dimensions
W x D x H (cm)
20.0” x 36.3” x 59.7”
(50.8 cm x 92.2 cm x 151.6 cm)
Rated Voltage
208; 220; 240; 380; 400; 415; 480; 600 VAC
(Determined by Input Transformer internal to the unit)
Voltage Variation
+10% to -30%; (-15% to -30%****)
Rated Frequency
50/60 Hz
Input Cables Required
3 phase ; 3 Wire + GND
Dual Input Option Cables required
3 phase ; 4 Wire + GND
* Power Factor
Greater than 0.98 when in inverter mode
Required Input kVA
16 kVA
26 kVA
Walk-in Function
From 20% to 100% over 5 seconds
Inrush Current
Less than 8 times the rated current under synchronous operation
Current Limit
115% maximum
Input
* Harmonic Currents
Less than 8.5%
Less than 5.5%
DC Nominal (Voltage Range)
288 VDC (216 – 332 VDC)
Float Charge (Regulation)
324.0 VDC (
±
2%)
Ripple Voltage
0.5 V R.M.S.
**Rated Back-up Time
Refer to Battery System Manual
Battery
Rated Charge Current
10.0 Amps
Rated Voltage
(Determined by Output Transformer internal to the unit)
Rated Current
VA / Nominal Output Voltage / 1.73
Rated Power Factor
0.8 lagging
Output Cables Required
3 phase ; 4 Wire + GND
Voltage Regulation (phase-phase)
±
5% (0 – 100% balanced load);
±
6% (0 – 100% unbalanced load)
Voltage Adjustment Range
±
5V Manually from key pad
Phase Displacement
±
2
°
(0 –100% balanced load);
±
4
°
(unbalanced load)
Rated Frequency
50 / 60 Hz
Frequency Regulation
±
0.1% in free running mode
Frequency Synchronous
±
0.5/1.0/1.5 Hz (
±
1.0 Hz. std.)
switch selectable by qualified technician
Frequency Slew Rate
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
Voltage Transients
(Recovery time: 50 ms)
±
5% (100% load step change);
±
3% (loss or return of input voltage);
±
8% (transfer from bypass to inverter)
Inverter Overload Capacity
125% for 90 sec; 150% for 30 sec
Bypass Overload Capacity
1000% for 10ms; 125% for 10 min.
Crest Factor
2.5 – 3.0 within the kW range
Neutral Line Conductor
1.73 (200%) times line rating
Harmonic Voltage Distortion
1.5% max (linear load)
Output
Inrush Current protection
Automatic Transfer to bypass, then retransfer to inverter
Efficiency (Typical)
AC/DC/AC: 75%; DC/AC: 82%
AC/DC/AC: 77%; DC/AC: 83%
Heat loss to be removed
12,662 BTU/hr (3,190 kcal/hr)
19,041 BTU/hr (4,797 kcal/hr)
Audible Noise
60dB (A) at 1 meter from the front of the unit
Operating Temperature
32 – 104
°
F (0 – 40
°
C); optimal temperature is 77
°
F (25
°
C)
Operating Humidity
30 – 90% RH (non condensing)
Environment
Altitude ***
Less than 2000 meters
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
(****) Prolonged operation at this level requires some derating of the output capacity.
4200FA CT/XT User’s Manual
27