4.1.2 Power Connections 15/25/30 kVA with Internal Transformer
The following illustrates the wiring connections from the power distribution panel (not part
of the UPS) to the terminal block of the 15/25/30 kVA UPS Models.
Ensure the three-phase commercial power input is connected for clockwise rotation. The
UPS output function is disabled if the input power is not phased for clockwise rotation.
* Customer-provided breaker for units with optional Bypass Input.
CUSTOMER-PROVIDED AC DISTRIBUTION PANEL
TO BATTERY SYSTEM GND
TB4
INPUT GROUND RESISTANCE
LESS THAN 10 OHMS
TB1
Optional Bypass Input:
3-Phase, 3-Wire
*208 V requires 3-Phase,
4-Wire Wye
16
4200FA CT/XT User’s Manual