Installation
Valve Adjustment
Chart showing the maximum one-way wire distance
between controller and valve solenoid *
feet
meters
Common Wire
Gauge Size
Control Wire Gauge Size
18
16
14
12
10
8
6
18
2040
2520
2940
3280
3540
3720
3860
622
768
896
1000
1079
1134
1177
16
2520
3260
4000
4660
5220
5620
5920
768
994
1219
1420
1591
1713
1804
14
2940
4000
5180
6360
7420
8300
8960
896
1219
1579
1939
2262
2530
2731
12
3280
4660
6360
8240
10100 11800 13180
1000
1420
1939
2512
3078
3597
4017
10
3540
5220
7420
10100 13180 16060 18770
1079
1591
2262
3078
4017
4895
5721
8
3720
5260
8300
11800 16060 20800 25540
1131
1603
2530
3597
4895
6340
7785
6
3860
5960
8960
13180 18700 25540 33080
1177
1817
2731
4017
5700
7785
10083
• Note the flow direction arrow in the side of the
valve body and install accordingly.
• The valve can be installed at any angle without
affecting operation.
• Use direct-burial irrigation control wire for
connection from the controller to valves.
• Leave a 12” (305 mm) wire expansion loop at each
valve location on long-run wire lengths.
• Waterproof wire splice connectors are absolutely
essential for proper electric control system
operation. Follow the installation instructions
provided by the connector manufacturer for
optimum performance.
*
Distances specified under the following
conditions: minimum voltage: 20 VAC, amperage:
0.12A, operating pressure: 150 psi (10,3 bar).
(if required)
(305 mm)
• Close the valve by turning the Flow Control Handle fully clockwise, just until resistance is felt
- do not overtighten!
• Remove the EZReg dial protective cover (if installed). Turn the control dial until the pointer
indicates the desired downstream pressure (5 to 100 psi) (,34 - 6,9 bar).
Note
: One revolution of the control dial adjusts the pressure setting approximately 10 psi (,69
bar). A minimum of 10 psi (,69 bar) pressure differential between the valve inlet and outlet is
required for proper EZReg operation.
• Pressurize the main supply line to the valve. Confirm that all pipe connections are properly
sealed.
• Actuate the valve either electrically at the controller, or manually by turning the Manual Bleed
knob counterclockwise solely until the valve opens.
• Turn the Flow Control Handle slowly counterclockwise to adjust sprinkler operation.
• To confirm outlet pressure, remove the poppet valve cap, located directly below the EZReg.
Attach a water-pressure test gauge to the poppet valve for a direct reading. Adjust pressure as
preferred.
Important: The EZReg assembly can be removed for service while the valve is pressurized.
However, the valve must not be operated with the EZReg assembly removed.
• Close Manual Bleed knob (if necessary) to close valve.
© 2016 The Toro Company • Irrigation Division • 1-877-345-8676
Form Number 373-0544 Rev. B