background image

2

1.

Make sure unit is grounded (earth ground).

2.

If remote overrides are used, make sure these unpowered wires are not run in
the same conduit as the load wires or supply voltage for the unit.

3.

Controller must have its own power source, i.e., no outlets or other loads
attached to the same supply source as the controller. Supply wire (hot) must be
run separately from load wire. Do not jump H terminal to load side. Controller
shall not be placed in any other enclosure other than its’ own or warranty will be
void. Consult factory for outdoor applications.

4.

The controller is to be installed where temperatures do not exceed 120°F or
below 32°F. For trouble free operation it should not be exposed to vibration,
dust, corrosive sprays or condensing atmospheric conditions.

5.

Control relays are SPDT dry contacts (unpowered) with LED indication when
relay is energized (when common and normally open close).

6.

To install unit open front cover to the left and lift off to remove.

7.

Make sure to mount unit so that it is at a convenient eye level for viewing
display and operating key board.

8.

Place unit at desired location and mark center of key hole on back of enclosure,
using #10 sheet metal screws or other suitable fastening device.

9.

Hang enclosure by key hole, locate lower left and right mounting holes and
fasten using 2 additional screws.

10.

A.

Use knockouts on bottom of enclosure for conduit connections.

B.

Do not run any wires from the back of the board.

11.

Connect all your load wires and identify them on the supplied schedule sheet.

12.

Connect your dedicated 120 VAC line to the left hand side of your terminal
board marked Hot and Neut. 

Note. Be sure unit is grounded. (Convenient

ground terminal is located at the bottom back of the case.)
Do not jump H to any other terminal.

13.

Slide Battery Switch to “ON”.

The controller is now ready for scheduling.

Please refer to the users instruction portion of this manual for scheduling
instructions.

Please see additional instructions provided to change from standard to automatic
daylight savings.

For circuits with high electrical noise, utilize the surge suppressors (supplied) across
the switched terminals.

TORK Z400B

INSTALLATION GUIDE

Summary of Contents for Z400B

Page 1: ...O TU WE TH FR SA HO 1 BLOCK START DATE END DATE RUN SET YEAR DATE TIME HOLIDAY SCHEDULE OVERRIDE ASTRO 1 SUN 2 MON 3 TUE DELETE 4 WED 5 THU 6 FRI REVIEW 7 SAT 8 HOL 9 AM PM MODE SELECT ADV 0 ENTER ON...

Page 2: ...igure 1 Installation Guide 2 Unit Features 3 Key Functions 3 Programming Summary 3 Setting the schedules 4 Reviewing the settings 6 Unit Specifications 7 Daylight Saving Addendum 7 Accessories Applica...

Page 3: ...OCK START DATE END DATE RUN SET YEAR DATE TIME HOLIDAY SCHEDULE OVERRIDE ASTRO 1 SUN 2 MON 3 TUE DELETE 4 WED 5 THU 6 FRI REVIEW 7 SAT 8 HOL 9 AM PM MODE SELECT ADV 0 ENTER ON OFF DUTY CYCLE 2 3 4 5 6...

Page 4: ...unit so that it is at a convenient eye level for viewing display and operating key board 8 Place unit at desired location and mark center of key hole on back of enclosure using 10 sheet metal screws o...

Page 5: ...ime of operation days of the week etc ENTER Sets the information being entered into the unit s memory PROGRAMMING SUMMARY RUN MODE Displays the current time AM PM format only day of week and channel s...

Page 6: ...Month Day Press ADV The display will show the same as before except that the END DATE LED will be lit instead of the START DATE LED Program the end date for the block Month Day Press ENTER The same bl...

Page 7: ...HOLIDAY SCHEDULE SET To program a holiday schedule proceed as outlined in the SCHEDULE SET section except select HO as the day selection That schedule will occur on all single day holidays as well as...

Page 8: ...OFFSET 00 to 99 minutes press AM PM for plus or minus OFFSET see above 2 Press ENTER to set ASTRO settings to memory Now next channel to be programmed begins to flash ASTRONOMIC WITH TIME SCHEDULE If...

Page 9: ...10 VAC 50 60 Hz Power Consumption 12VA Max Output Circuits SPDT Unpowered Contacts Contact Rating 10 Amps Resistive 120 240VAC 10 Amps Resistive 30 VDC 1 4 H P 120VAC 1 3 HP 240 VAC 360 Watts Tungste...

Page 10: ...to 95 When control turns ON day thermostat will override night setting and cool to 76 to 78 day setting REMOTE TIMED OVERRIDES 8 TORK MODEL Z400B TERMINAL BLOCK NO C NC OPEN CLOSE C 120 VAC LINE NEUTR...

Page 11: ...9 LOAD ASTRONOMIC LATITUDE S M T W T F S H SUNSET OFFSET SUNRISE OFFSET S M T W T F S H ON OFF TIME NO SUNSET TO SUNRISE SCHEDULE DUTY CYCLE OFF MIN ON MIN REMOTE OVERRIDE TIME MINUTES...

Page 12: ...10 LOAD ASTRONOMIC LATITUDE S M T W T F S H SUNSET OFFSET SUNRISE OFFSET S M T W T F S H ON OFF TIME NO SUNSET TO SUNRISE SCHEDULE DUTY CYCLE OFF MIN ON MIN REMOTE OVERRIDE TIME MINUTES...

Page 13: ...11 LOAD ASTRONOMIC LATITUDE S M T W T F S H SUNSET OFFSET SUNRISE OFFSET S M T W T F S H ON OFF TIME NO SUNSET TO SUNRISE SCHEDULE DUTY CYCLE OFF MIN ON MIN REMOTE OVERRIDE TIME MINUTES...

Page 14: ...12 LOAD ASTRONOMIC LATITUDE S M T W T F S H SUNSET OFFSET SUNRISE OFFSET S M T W T F S H ON OFF TIME NO SUNSET TO SUNRISE SCHEDULE DUTY CYCLE OFF MIN ON MIN REMOTE OVERRIDE TIME MINUTES...

Page 15: ...13 LOAD S M T W T F S H ON OFF TIME NO DESCRIPTION DUTY CYCLE OFF MIN ON MIN REMOTE OVERRIDE TIME MINUTES...

Page 16: ...14 LOAD S M T W T F S H ON OFF TIME NO DESCRIPTION DUTY CYCLE OFF MIN ON MIN REMOTE OVERRIDE TIME MINUTES...

Page 17: ...15 LOAD S M T W T F S H ON OFF TIME NO DESCRIPTION DUTY CYCLE OFF MIN ON MIN REMOTE OVERRIDE TIME MINUTES...

Page 18: ...16 LOAD S M T W T F S H ON OFF TIME NO DESCRIPTION DUTY CYCLE OFF MIN ON MIN REMOTE OVERRIDE TIME MINUTES...

Page 19: ...ol has been improperly installed or altered or damaged through misuse or by accident neglect misapplication fire flood or Acts of God TORK assumes no responsibility for any damages to people property...

Reviews: