Tork DGLC Installation & Operation Manual Download Page 3

at 1 to 2 footcandles. If adjusted to the extreme
right (MAX position), the ON relay will close at
approximately 100 footcandles. (There is a 2 - 4
second built-in delay).

IMPORTANT: The potentiometer allows you to
adjust a turn ON at 1 to 100 footcandles. OFF will
be 3 times the ratio of the ON foot candle level.
Light level adjustment is the same for both
circuits.

IMPORTANT NOTES CONCERNING THE
PHOTOCELL INPUT:

1. An ON event must be scheduled prior to sun-

set in order for the photocell to activate circuit
#1. Timer can then be scheduled OFF and
later ON again before sunrise for any desired
days.

2. Circuit #2 is directly controlled by photocell

and light level adjustment. It is not governed
by timer or the manual override.

3.  Photocell can be wired up to 500 feet from

timer using 2 wire, #18 to #22 AWG, between
input terminal and photocell.

4.  Do not put excessive pressure on potentiome-

ter. Use thumb and forefinger or small screw-
driver to adjust for light level. Avoid shorting
screwdriver to upper board.

5.  Light level adjustment operates only with Tork

Photocell Model EPC1.

KEY FUNCTIONS 

DAY/MONTH: Press to advance the day in the
CLK mode. Press to advance the Month in the
DATE mode.

HOUR/DATE: Press to set the Hours in the CLK
mode and in the Schedule SET mode. Press to
advance Date in the DATE mode.

3

LIGHT LEVEL ADJ.

MIN

MAX

DAY

MONTH

HOUR

DATE

MIN

YEAR

OVER-

RIDE

MODE

SP DAY

ON/OFF

ENTER

MIN/YEAR: Press to set the Minute in the CLK
mode and in the Schedule SET mode. Press to
advance Year in the DATE mode.

OVERRIDE: Press to alter the Load status and/or
to Override scheduled event on circuit #1 only.

MODE: Press to advance to next mode without
affecting the scheduled memory information.
Sequence is: RUN, CLK, DATE, schedule SET. In
the SET mode, unit automatically reverts to
the RUN mode if no entries are made for 5
minutes.

SP DAY: Press during RUN mode to execute the
“SPECIAL DAY’ schedule everyday. LCD will dis-
play D in upper right corner. Pressing SP DAY
again will toggle the unit back to normal 7 day
program operation.

ON/OFF: Pressing each time will select an ON or
an OFF. Multiple OFF’s may be scheduled to can-
cel override ON’s.

ENTER: Press to store the displayed information
into memory. Information will not be stored
until ENTER is pressed.

NOTE: During settings, each press of the key will
advance one number. For rapid advance, hold
key in.

SELECT AM/PM OR 24 HOUR 

MILITARY FORMAT:

Upon powering up the unit the LCD will display
the model number 100. The LCD will next display
12H which is an automatic (AM/PM) format.

Press ENTER to keep AM/PM format or press
HOUR key to alter to 24 hour (Military) format and
then press ENTER.

4

Summary of Contents for DGLC

Page 1: ...enclosure Push tab on right to swing unit to the left and remove 3 Mount the enclosure at eye level using screws or other suitable fastening device Bring supply and load wires in through the bottom o...

Page 2: ...step 1 above and connect wires to unit as per suggested wiring diagrams See illustration on enclosure label 6 The photocell can be mounted directly through a standard 1 2 knockout Connection to junc t...

Page 3: ...er to adjust for light level Avoid shorting screwdriver to upper board 5 Light level adjustment operates only with Tork Photocell Model EPC1 KEY FUNCTIONS DAY MONTH Press to advance the day in the CLK...

Page 4: ...hout affecting the scheduled memory information Sequence is RUN CLK DATE schedule SET In the SET mode unit automatically reverts to the RUN mode if no entries are made for 5 minutes SP DAY Press durin...

Page 5: ...entering the current month date year The unit will add one hour on the first Sunday in April and subtract one hour on the last Sunday in October You never need to look up the tables or enter the spri...

Page 6: ...s DATE key to set today s date Press YEAR key to set present year Press ENTER key Unit now stores present date NOTE If the unit has correct entry for the calen dar then the unit will go into the SET m...

Page 7: ...et will repeat for as many days as you want If no schedule was entered the circuit 1 load will not turn ON To return to normal 7 day program operation press the SP DAY key again and the letter D will...

Page 8: ...and ON OFF keys can all be used to modify the settings You can use the first three keys to modify when the event will take place and the ON OFF key to change an ON event to an OFF event or visa versa...