DXR-GO Switch Installation, Operation & Maintenance
502.969.8000
4
Don’t forget!
TopWorx has a complete line of breathers,
flow controls, regulators and filters.
Check out
www.topworx.com
or call us at
502.969.8000
for more details
DID YOU KNOW?
TopWorx manufactures the globally-known
GO Switch Leverless Limit Switch, which
comprises a full line of harsh environment
sensors. If your application is very cold, very
hot, under water or in a caustic atmosphere,
then GO Switch has the answer.
Spool Valve Specifications
Medium
Dried, filtered air (40 micron)
Max Operating
Pressure
100psi (0.7 MPa) (6.89Bar)
Min. Operating
Pressure
30psi (0.28 MPa) (2.76Bar)
Ambient
Temperature Range
Refer to Product Nameplate Marking
Flow Coefficient
1.2Cv or 3.0Cv (1.0 for ColdTemp™)
Environment Rating
Type 4, 4X, IP67
Port Size
1/2” NPT for 3.0Cv valve
1/4" NPT for 1.2Cv valve
Manual Override
Available in Latching/Non-Latching Push
Type & Palm Actuator Type
Valve Body
Available in Hardcoat Anodized
Aluminum, 304, or 316 Stainless Steel
Valve Seals
Spool Seals: Buna-N
Valve Body Seals available in
Buna-N, Silicone, EPDM & Viton.
ColdTemp™ Spools are lap-joint
technology containing no seals.
Pneumatic Hookup Procedures
Prior to connecting the supply air to the spool valve, flush the system to
remove any debris or contaminates. Galvanized pipe can easily flake and
contaminate the system and therefore is not recommended. A 40 micron
point of use filter at every device is recommended.
4-Way Spool Valves
The TopWorx spool valve is a 5 port, 4-way valve driven by an internally
mounted pilot valve. The spool valve supply port and work ports are marked
as follows:
Highly Recommended
TopWorx highly recommends Locktite 567 brand thread sealant. Do not use
a hard setting pipe compound. If Teflon thread seal tape is used, start the
wrap on the second thread from the leading thread of the fitting. This will
prevent tape shreds from contaminating the spool valve seals.
Flow controls (AL-M21) or Breathers (AL-M31) should be installed in the
exhaust ports to keep debris from falling into the spool valve and damaging
the seals. This must be addressed prior to installation, or storage.
***NEVER PLUG, OR BLOCK, PORT 5***
Supply
Port to Open
Port to Close
Always install vents
or speed controls
Supply
DOUBLE ACTING ACTUATORS
SPRING RETURN ACTUATORS
1
3
5
2
4
1
3
5
2
4
Port to Open
Plug