THE ACTUATOR INSTALLATION CAN BE PERFORMED EXCLUSIVELY BY COMPETENT AND QUALIFIED
TECHNICAL PERSONNEL SATISFYING THE PROFESSIONAL AND TECHNICAL REQUIREMENTS FORE
SEEN BY THE LAWS IN FORCE IN THE COUNTRY OF INSTALLATION.
5.1- GENERAL INSTRUCTIONS
THE ACTUATOR INSTALLATION MUST BE PERFORMED EXCLUSIVELY WITH CLOSED WINDOW.
THE FITTING SURFACE FOR THE BRACKETS MUST BE PERFECTLY FLAT AND/OR SMOOTH.
THE CORRECT ADJUSTMENT OF THE WINDOW FRAME CLOSING ASSURES THE LIFE AND THE
TIGHTNESS OF THE SEALS, AS WELL AS THE GOOD OPERATION OF THE ACTUATOR.
WITH OPEN WINDOW FRAME, VERIFY THAT THE STROKE IS SOME CENTIMETRE LOWER THAN THE
STROKE LIMITED BY WINDOW FRAME MECHANICAL LIMIT DEVICES.
THE ACTUATOR PERFORMANCE MUST BE SUFFICIENT TO ASSURE THE CORRECT MOVEMENT OF THE
WINDOW. IT IS COMPULSORY TO VERIFY THE THRUST OR TRACTIVE FORCE ACCORDING TO THE TYPE
AND WEIGHT OF THE WINDOW. IT IS FORBIDDEN TO EXCEED THE LIMITS CONCERNING TECHNICAL
DATA (PAR. 3.1).
CHECK THE ADEQUACY OF THE WINDOW AND THE SUITABILITY OF THE MATERIALS OF THE WINDOW
AND/OR FRAME ON WHICH THE ACTUATOR WILL BE FASTENED. AND IT MUST ENSURE A GOOD
SUPPORT OF THE ACTUATOR-WINDOW ASSEMBLY DURING THE MOVEMENT.
TO GUARANTEE THE DEGREE OF IP PROTECTION STATED IT IS NECESSARY TO TIGHTEN THE SCREWS
OF THE COVER AND CABLE GLAND WITH A 1.5Nm PAIR
BEFORE PERFORMING THE INSTALLATION OF THE ACTUATOR ON BOTTOM HUNG WINDOWS, VERIFY
THAT ON BOTH SIDES OF THE WINDOW TWO COMPASS STROKE LIMIT DEVICES ARE INSTALLED IN
ORDER TO AVOID THE ACCIDENTAL FALL OF THE WINDOW.
THE ELECTRIC CONNECTION OF THE ACTUATOR MUST BE DONE BY THE INSTALLER WITH BIPOLAR,
TRIPOLAR OR MULTIPOLAR CABLES, WITH 0.75mm2 SECTION, AND EXTERNAL DIAMETER FROM 4.5mm
TO 10mm, ACCORDING TO THE MACHINE TYPE (24V, 230V, TANDEM) . FOR EXTERNAL INSTALLATIONS IT
IS NECESSARY TO CHOOSE SUITABLE CABLES FOR THIS USE TYPE H05RN-F. IT IS RECOMMENDED TO
RESPECT THE COLOR CODE AS INDICATED IN THE TECHNICAL INSTALLATION STANDARDS.
THE ELECTRIC CONNECTION OF THE ACTUATOR (PAR.1 ) CAN BE PERFORMED ONLY BY COMPETENT
AND QUALIFIED TECHNICAL PERSONNEL FORESEEN BY THE LAW IN FORCE IN THE COUNTRY OF
INSTALLATION WHO CAN ISSUE TO THE CUSTOMER A DECLARATION OF CONFORMITY FOR THE
CONNECTION AND/OR PLANT CARRIED OUT.
1
BEFORE PERFORMING THE ELECTRIC CONNECTION OF THE ACTUATOR, VERIFY THE CORRECT
INSTALLATION ON THE WINDOW
THE CONNECTION OF MODEL S80/24V HAS TO BE CARRIED OUT WITH VERY LOW VOLTAGE SAFETY
FEEDER PROTECTED AGAINST SHORT CIRCUIT.
THE SECTION OF THE MAINS CABLES MUST BE PROPERLY SIZED ACCORDING TO THE ABSORBED
ELECTRIC POWER (SEE RATING PLATE AND “CE” MARKING).
5.3- ELECTRIC CONNECTIONS
THE MAINS TO WHICH THE ACTUATOR IS CONNECTED MUST COMPLY WITH THE REQUIREMENTS OF THE
LAWS IN FORCE IN THE COUNTRY OF INSTALLATION, AS WELL AS SATISFY THE TECHNICAL FEATURES
GIVEN IN PAR.3.1 AND ON THE RATING PLATE AND THE “CE” MARKING.
ANY TYPE OF ELECTRIC MATERIAL (PLUG, CABLE, TERMINALS, ETC.) USED FOR THE CONNECTION
MUST BE SUITABLE FOR THE USE, WITH “CE” MARKING, AND COMPLYING WITH THE REQUIREMENTS
FORESEEN BY THE LAWS IN FORCE IN THE COUNTRY OF INSTALLATION.
Perform the installation as described in
Chapter 10 : DRAWINGS / INSTALLATION INSTRUCTIONS.
5.2- INSTALLATION
15
INSTALLATION AND USE INSTRUCTIONS
INSTALLATION AND USE INSTRUCTIONS
S80
INSTALLATION-5