Page 05 KKAI808PE01-A/0-20130904
Parameter name
e
g
n
a
r
g
n
it
t
e
S
n
o
it
a
c
i
d
n
I
Ex-factory setting
Setting menu
Measured value amendment
OUT2 control cycle ( setting range can
)
Dead area for heating & cooling control
Alarm hysteresis 1
Alarm mode 1
Alarm hysteresis 2
Alarm mode 2
Alarm hysteresis 3
Alarm mode 3
8. Menu Parameter
Manual / auto setting: 0 Manual 1: half-auto
Output function setting menu
Integral time
Control mode. 0 ON/OFF control 1 Heating control
Start Auto-tuning manually
2: auto Start Auto-tuning automatically after power on
Alarm 1 setting value
Alarm 2 setting value
Alarm 3 setting value
2 Cooling control 3 Heating & cooling control
Proportional coefficient (P=0: ON / OFF control)
ON/OFF control hysteresis
Derivative time
OUT1 control cycle: Current output is 0;
Cooling proportional coefficient
1
1
1
1
1
1
1
SSR output is 1; the setting range of SSR output can
4) In normal display status, press key for a few seconds to show the parameter setting menu of
program segment control.
5) In normal display status, press key for a few seconds to enter into status setting value of program
segment control. You can choose RUN, STOP and HOLD three status in this segment.
Example Here is a control process with below requirement, the relevant setting is on the right side:
1) Temperature raise to 300
SV01=300 ST01=0;
2) Temperature raise from 300 to 500 (raise 10 degrees/ min) SV02=500 ST02=20
3) Temperature falls to 150
SV03=150 ST03=0;
4) Temperature is keep at 150 for 60 minute, and then SV04=150 ST04=60
Program jumps to No.10 segment
ST05=
-
10
6) Temperature falls to 25 at No.10 segment
SV10=25 ST10=0;
7) Program control stops running at No.11 segment.
exit the segment and control the temeprature according
to the SV
(
SV10=25
)
setting value
ST11=-51;
0001, prohibit to modify SV; 0010, prohibit to modify Menu parameter;
0011, prohibit to modify SV and Menu;
Input function setting menu
Communication setting menu
Lower limit of control output
Upper limit of control output
Input signal type
Please refer to input signal table
Lower display limit of input signal
Upper display limit of input signal
Decimal point setting. Only effective for analog signal input
Filter constant
Lower limit display for transmit current output
(with current transmit output can workable)
Baud rate
Meter communication address
Please refer to input signal table
Please refer to input signal table
0: unit of celsius, 1: unit of fahrenheit
Higher limit display for transmit current output
(with current transmit output can workable)