PRECAUTIONS
Transformers should be installed in an accessible location. Magnetic transformers generate heat and must be
installed in locations where there is free-air circulation. Electronic transformers require less space to dissipate
heat, but they too should be installed in accessible locations with free-air circulation.
For additional information, please refer to the instruction manual provided with your transformer.
Secondary Circuit Protection
Transformers are provided with circuit breakers to protect secondary circuits. The maximum size circuit breaker on a
transformer is 25 amps, but the circuit wired to the breaker MUST NOT EXCEED 20 AMPS.
There are several transformer sizes available, and different size breakers installed in them. Below is a selection of trans-
formers with their respective circuit limitations.
Larger capacity transformers with multiple out-
puts can be centrally located and feed fixtures
in either direction.
Input Voltage
Transformer
Do not exceed maximum fixture length
Do not exceed transformer output rating
Transformer Location
The maximum recommended distance between the fixture and the transformer varies, based upon the load of each fix-
ture and the size of secondary wire feeding the fixture. It is impossible to give a definitive distance without considering
all the variables. Electrical engineers and contractors can calculate these distances. Should you need guidance, consult
the factory.
Step 4: Transformer Instructions
25 A
500 Watt
Transformer
Max. Load 20 Amps
480 Watts Max.
15 A
300 Watt
Transformer
Max. Load 12.5 Amps
300 Watts @ 24 VAC
250 Watt
Transformer
15 A
Max. Load 10.4 Amps
250 Watts @ 24 VAC
7 A
100 Watt
Transformer
Max. Load 4.1 Amps
100 Watts @ 24 VAC
25 A
25 A
1000 Watt
Transformer
Max. Load 20 Amps
480 Watts @ 24 VAC
Max. Load 20 Amps
480 Watts @ 24 VAC
960 Watts Max.
25 A
25 A
750 Watt
Transformer
Max. Load 20 Amps
480 Watts @ 24 VAC
Max. Load 20 Amps
480 Watts @ 24 VAC
750 Watts Max.
Advantage Instructions
Page 5
Version 1.1