Toho Electronics TTM-300 Series Instruction Manual Download Page 18

 

17 

⑩ 



  SV Limiter Low  Set Number of SV Limiter Low. 

Setting range: Setting range low

~ 

             



-50)℃

/

 

 

 

⑪ 



  SV Limiter

 

  High

 

Set Number of SV Limiter High. 
Setting range: (



+

50

)

/

 

                   

Setting range high

 

 

Initial  value  is  different  by  input. 
Refer  to 

“7.SETTING  RANGE 

AND 

INDICATION 

RANGE 

TABLE”.

 

 

  Select the start SV at the starting of 
the run. 



 

    SV start 

 



 

    PV start 

 

⑫ 



 

Start SV 
selection 

   

 

 



  

 

 
 

⑬ 



 

Starting 
temperature 

  Set  the  temperature  value  of  SV 
start 
Setting Range:





 

 

or 



 

Displays when   



  is 



.

 

 

  Select operations for power input. 

 

  Reset and start 

 

 

  Operation at power 

 

⑭ 



 

Power ON 
operation 
selection 

   

 

 

  

 

 

Select Event output functions 
  1 and 2. 

 

  Release function 

 

  PV event output 

 

  Time signal 

 

  End signal 

 

 

  Loop abnormal event 

 

⑮ 

 



 



 

Event 1, 2 
functions 

   

 

 

 

Displays  with  options  of  Event 
output 1, 2. 

 
 

  Select Process value for event

 

  output functions 1 and 2. 



 

    *※ 

 



 

Displays when 



  is 

.

   

 

* 

  FUNCTIONS(select with 

  key) 

※ 

ADDITIONAL FUNCTIONS 

 

  Release functions 

 

(select with 

  key) 

 

  Deviation high/low limit 

 

Release function 

 

  Deviation high limit 

 

Event output hold 

 

  Deviation low limit 

 

Stand-by sequence 

 

  Deviation range for 

 

Abnormal process value 

 

  high and low limit 

 

Event output hold + 

 

  Absolute value high/low limit 

 

stand-by sequence 

 

  Absolute value high limit 

 

Event output hold + 

 

  Absolute value low limit 

 

  Abnormal process value 

 

 

 

  Range of absolute value 
  high and low limits 

 

 

 

 

Stand-by se 
  Abnormal process value 

 

 

Event output hold + 
  Stand-by se 
  Abnormal process value 

 

 

⑯ 

 



 



 

 

Process value 
event output 
functions 1,2

 

 

⑰ 
⑱ 

 

 



 



 



 



 

Process 

value 

event output 
1 and 2. 
High/Low 
limit setting 

Set  the  temperature  of  the  process 
value event output 

Setting range: 
  -199.9to 999.9

℃/

   

      -199 to 999

℃/

 

 

or 



 

Displays according to the 
setting of process value 
event output function. 
 

 

 

Summary of Contents for TTM-300 Series

Page 1: ...d also equipped the communication functions using RS 485 as an option Please go through this Instruction Manual carefully and use the unit in proper manner CONTENTS 1 NOTICE WARNING BEFORE USAGE 2 INS...

Page 2: ...it and may cause a fire Never remodel the unit for prevention of malfunction of unit and a fire Types of Input Thermocouple R T D and Output cannot be changed after receiving the unit Check if all the...

Page 3: ...nging TIME or TEMPERATURE indicate RUN STOP Changing Reset mode or Run mode PTTN STEP RUN mode Changing PTTN STEP confirmation mode RESET RUN mode RESET mode The details of Operation Keys to be referr...

Page 4: ...he unit at the following proper locations Temperature and Humidity are within the limit of operation environment Away from the gas of sulfide and corrosion Less dust and oily smoke Less mechanical vib...

Page 5: ...13 14 10 11 Run signal 13 14 Curr Volt TTM 3 0 4 TTM 3 0 5 2 3 24VAC or DC 1 FG 2 3 85 264VAC 1 FG 4 5 Comm TR A TR B 4 5 RUN signal 3 4 SSR Drive Volt Curr Volt output 5 Relay contact 3 NC 4 NO 8 9 1...

Page 6: ...e make sure to confirm the name labels i e Input terminal Power source terminal and Option terminals etc beside the each wire The crimp terminals for wiring should be fit with the nuts of M3 5 As for...

Page 7: ...Value RAMP STEP SOAK STEP SV start It will start from the setting value at the starting time of operation which to be treated as the PV Process variable or the target SV Setting Value PV start Operat...

Page 8: ...viation Example for Event Output 1 Absolute Value Example for Event Output 1 1 High and Low limit 5 High and Low limit 2 High limit 6 High limit 3 Low limit 7 Low limit 4 High and Low limit range 8 Hi...

Page 9: ...ic it compensates MV Manipulation Value worked out by PID control and controls not to Overshoot or Undershoot FUZZY Strength This means the strength of compensation Strength 1 5 against MV worked out...

Page 10: ...setting of each Control Temperature area Also please make setting of other control parameter as required The setting of Key Input is valid in memory even if the power turned OFF High Temperature cont...

Page 11: ...emp area by and key Press MODE key High Temperature Proportional band Press MODE key High Temperature Integral time Press MODE key High Temperature Differential Time Press MODE key Setting Proportiona...

Page 12: ...Setting target SV by key In case the current step to be set as final step press TIME TEMP key to blink target setting For canceling this press TIME TEMP key again Setting Step Time by key If the cont...

Page 13: ...p Proportional band point Middle temp Press Mode key final step Press Mode key Operation volume Number of Integral time lower limit operation middle temp Press Mode key Press Mode key Press Mode key O...

Page 14: ...y Communication Address Press Mode key Response Delay Time Press Mode key Change over Communication mode Press Mode key Key Lock function Press Mode key Return to Number of pattern ON OFF Control Cont...

Page 15: ...mode BLIND mode Press MODE key Press MODE key Press MODE key Press MODE key Indication at Setting Value means Display exist and means no Display For canceling BLIND mode turn the Power OFF once and tu...

Page 16: ...me The Set value display blinks while the Wait is on operation Wait is on operation And the process value appear alternately on a PV display area at the end of pattern operation End of pattern operati...

Page 17: ...nput type can be selected or The initial value varies by the types Thermocouple Input Type RTD INPUT TYPE Input Type Input Type K thermocouple PT100 J thermocouple JPT100 T thermocouple R thermocouple...

Page 18: ...ct Process value for event output functions 1 and 2 Displays when is FUNCTIONS select with key ADDITIONAL FUNCTIONS Release functions select with key Deviation high low limit Release function Deviatio...

Page 19: ...Event output 1 2 Time Signal On Time On Delay time Set the Time signal ON Time Setting range 0 99 hrs 59 min If select 2 for Time signal function set ON Delay Time Displays when are Event output 1 2...

Page 20: ...ameter per pattern setting mode No Character Name Description Initial Value Display condition Remarks Step temperature setting Set the temperature value for step Setting range Step time setting Set th...

Page 21: ...ddle temperature area Setting range Highest limit of setting rang Setting unit Proportional cycle Set a proportional cycle on PID control Time proportional control Setting range 1 120 sec Displays whe...

Page 22: ...IEC 32 3270 4 2435 7 2 Setting range and Indicating range of R T D Input type Setting range Setting range with decimals Indication range Indication range with decimals 199 500 199 9 500 0 199 539 199...

Page 23: ...onnected Input type R T D Pt100 JPt100 switchable Allowable lead wire resistance 5 or less per wire Sampling time 0 5 sec same as output change frequency PV input area PV correct 199 9 999 9 or 199 99...

Page 24: ...AND INSPECTIONS Troubles Check points Display does not come out Is instrument correctly inserted in the case Are power terminals correctly connected Is power sufficiently supplied display Memory erro...

Reviews: