16
f) Common Parameter setting mode
No
Character
Name
Description
Initial
Value
Display conditions/Remarks
①
Number of Pattern Set Number of program patterns
Setting range: 1 - 64 patterns
②
Number of Steps
Set Number of steps of each pattern.
Setting range: 1 - 64 steps
The product of pattern No. and
Step Number should not
exceeds 64 as the maximum.
③
PV correction
Add PV correction value to
a process value to be entered.
Setting range:-199.9 to 999.9
℃/
-199 to 999
℃/
or
Select
℃/
for the PV display.
℃
④
℃/
Selection
Select the control type from the table below.
ON/OFF control, normal
ON/OFF control, reversed
PID control, normal
PID control, reversed
PID + fuzzy control, normal
⑤
Control type
PID + fuzzy control, reversed
Auto-tuning is always
Required, if Fuzzy control
selected.
I/O types are indicated and input
type can be selected.
*
or
The initial value varies by the
types.
※※**
*
Thermocouple Input Type RTD INPUT TYPE
※※
Input Type
※※
Input Type
K thermocouple
PT100
J thermocouple
JPT100
T thermocouple
R thermocouple
No alteration possible
N thermocouple
**
Output type
B thermocouple
Relay contact output
SSR drive output
Voltage output
⑥
Input /Output
type
Current output
Select if below decimal point is
required or not.
Decimal not required.
⑦
Decimal point
selection
Decimal required.
or
Decimal point is not displayed on
R, N, B thermocouples.
⑧
Manipulated
value lowest
limiter
On proportional control, set the lowest
value of manipulated control output.
Setting range: 0.0%
~
(Relay contact, SSR Output)
-10.0%
~
(Voltage, current output)
Displays when
are
,
,
,
.
⑨
Manipulated
value highest
limiter
On proportional control, set the highest
value of manipulated control output.
Setting range:
~
100.0%
(Relay contact, SSR Output)
~
110.0%
(Voltage, current output)
No
Character
Name
Description
Initial
value
Display conditions/Remarks