background image

 

CONTROLLER OPERATION

 

 
1. 

Switch in the “AUTOMATIC” setting 

 

The controller switches the blower on or off depending on the temperature of the sensor. 

 

Use the rotary knob to set the temperature above which the continuous operation of the blower is 
automatically switched off. 

 

If the temperature is higher than the set value, the blower switches on for 0

÷18 seconds every 6 

minutes (periodic boiler blow-through). The time setting can be adjusted using a small screwdriver (one 
full rotation corresponds to ca. 1 second) through the opening on the left-hand side of the housing next 
to the fuse base (factory setting: 6 seconds). 

 
Note: Blow-through should not be deactivated for safety reasons. 
 

 

After the CH boiler is extinguished and the temperature drops below 30

°C, the continuous operation of 

the blower is switched off, and periodic boiler blow-through is deactivated.

 

 

If the red indicator is lit, it denotes blower operation.

 

 

On

Off

Setting 

in scale

Periodic 

blow-through

Temp.

30°C

 

 
2. 

Switch in the “FIRE UP” setting

 

 

If the CH boiler is cold (temperature below 

30

°C), the blower is switched on to enable the firing of the 

boiler.

 

 

If the temperature rises above the setting in the scale, the continuous operation of the blower is 
switched off 

(as in the “AUTOMATIC” mode), and periodic boiler blow-through is performed.

 

 

On

Setting 

in scale

Periodic 

blow-through

Temp.

30°C

 

3. If (after boiler firing) the temperature exceeds 

30

°C, put the switch to the “AUTOMATIC” setting 

so that the blower is switched off after the boiler is extinguished. 
 

4. The controller is equipped with an electronic thermometer with a digital display for indicating the 
temperature on the boiler (range: 20-99

°C). 

 
 

SAFETY DEVICES 

 

The controller and the blower motor are protected by means of a 500 mA fuse which blows up in emergency 
situations (e.g. short-circuit in the motor or in the controller).  
An additional protective device is a thermal cut-out which switches off the blower independently of the 
controller when the temperature of the boiler exceeds 90

°C (the thermal cut-out is switched on again when 

the temperature drops by ca. 30

°C), e.g. in the event of pump or controller failure. 

 

 

Reviews: