172-65176MA-03  (UFO3 Series)  27  Aug 2015

 

13

 

Option: Insulation Cover 

 

 

When disassembling or removing the product, wait until the internal 

pressure equals atmospheric pressure and the surface of the product 

has cooled to room temperature. Disassembling or removing the 

product when it is hot or under pressure may lead to discharge of fluids, 

causing burns, other injuries or damage.

 

CAUTION 

 

One insulation cover set consists of a soft ceramic fiber case and 2 binding straps. 

Use the following procedures to install the insulation cover. (Installation, inspection, 
maintenance, repairs, disassembly, adjustment and valve opening/closing should be 
carried out only by trained maintenance personnel.) 

Attaching the Insulation Cover to the Steam Trap

 

1.  Allow the trap to cool to ambient temperature. 
2.  Open the cover along the Velcro strip. 
3.  Place cover evenly around the body with the arrow on the cover facing the same 

direction as the arrow on the trap body.   

4.  Reattach the Velcro strip. 
5.  Secure the ends of the cover around the trap inlet and outlet with the binding 

straps. 

Applicable insulation cover for UFO3-BN/UFO3F-BN: RK3 

放熱キラー

205 (8

1

/

16

)

70 (2

3

/

4

)

150 (5

7

/

8

)

80 (

3

1

/

8

)

70 (

2

3

/

4

)

40 (

1

9

/

1

6

)

100 (4)

6 (

1

/

4

)

15 (

9

/

16

)

Insulation Cover (side)

Insulation Cover (top)

Binding Strap (2 pc.)

Velcro Strip

Thickness: 0.2 (0.008)

Unit: mm (in) 

 

 

Summary of Contents for UFO3-BN

Page 1: ...03 UFO3 Series 27 August 2015 Free Ball Bucket Steam Trap UFO3 BN UFO3F BN Copyright 2015 by TLV CO LTD All rights reserved ISO 9001 ISO 14001 Manufacturer Kakogawa Japan is approved by LRQA LTD to IS...

Page 2: ...is out of the ordinary Also be sure to read this manual carefully before use and follow the instructions to be sure of using the product properly The Free Ball Bucket Steam Trap is suitable for appli...

Page 3: ...ation which poses a threat of death or serious injury WARNING Indicates that there is a potential threat of death or serious injury CAUTION Indicates that there is a possibility of injury or equipment...

Page 4: ...fluids Do not use excessive force when connecting threaded pipes to the product Over tightening may cause breakage leading to fluid discharge which may cause burns or other injury Use only under condi...

Page 5: ...to back pressure has a check valve TLV CK been installed 5 Is the inlet pipe as short as possible with as few bends as possible and installed so the liquid will flow naturally down into the trap 6 Ha...

Page 6: ...reventing it from closing against the drain jet allowing the discharge of all initial air and cold condensate 2 Entry of Steam When steam flows in the higher temperature causes the bimetal to expand r...

Page 7: ...ION Refer to the product nameplate for detailed specifications Model Maximum Allowable Temperature TMA Maximum Allowable Pressure Maximum Operating Temperature Nominal Diameter Maximum Differential Pr...

Page 8: ...use burns or other injury CAUTION Installation inspection maintenance repairs disassembly adjustment and valve opening closing should be carried out only by trained maintenance personnel 1 Before inst...

Page 9: ...e to steam leakage Normal Condensate together with flash steam is discharged intermittently and the sound of flow can be heard at the time of discharge Blocked Discharge Impossible No condensate is di...

Page 10: ...re no pieces of the old gasket left on the seating surfaces make sure the arrow points in the direction of condensate flow Cover Gasket Remove being careful not to damage the seating surface and clean...

Page 11: ...1 N m 10 kg cm NOTE Coat all threaded portions and orifice gasket with anti seize If drawings or other special documentation were supplied for the product any torque given there takes precedence over...

Page 12: ...ns Steam locking has occurred Perform a bypass blowdown or close the trap inlet piping and allow the trap to cool Steam is discharged or leaks from the outlet blowing steam leakage Build up of rust or...

Page 13: ...proper installation use handling etc by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or...

Page 14: ...ection maintenance repairs disassembly adjustment and valve opening closing should be carried out only by trained maintenance personnel Attaching the Insulation Cover to the Steam Trap 1 Allow the tra...

Reviews: