Installation of X-element 

Figure A

Figure B 

Spring clip 

Slot

Slot

X-element

X-element guide 

Cover

9. Troubleshooting

If the expected performance is unachievable after installation of the air vent, read chapter 5 and 
chapter 6 again and check the following points to take appropriate corrective measures.

No air is 
discharged 
(blocked) or 
discharge is 
poor

The X-element is stuck to the valve seat 
The valve seat is blocked

Clean parts

Steam is 
discharged or 
leaks from 
the outlet 
(blowing)
(steam leakage)

There is rust or scale between the 
X-element valve and valve seat

Clean parts

Steam is leaking 
from a place other 
than the outlet

The X-element is broken

Replace with a new X-element

Improper installation

Correct the installation

Air vent vibration

Lengthen the inlet piping and fasten it securely

Gasket deterioration or damage

Replace with a new gasket

Improper tightening torques were 
used

Tighten to the proper torque

The X-element valve and valve seat 
are damaged

Replace with a new X-element and/or 
cover (LA13L: also the valve seat)

Clean the valve seat, or replace with 
a new valve seat (LA13L) or cover

The screen is clogged

Clean parts

The air vent operating pressure exceeds 
the maximum specified pressure, or 
there is insufficient pressure differential 
between the air vent inlet and outlet

Compare specifications and actual 
operating conditions

Cause

Remedy

Problem

Part & No.

Body 1 / 
Cover 2

Cover Gasket 8
(LA13, LA13L)

Replace with a new gasket only if worn 
or damaged

Spring Clip 7

X-element 3

Valve Seat 4 
(LA13L)
X-element Guide 9 
(LA13L)
Screen 5

Insert carefully without bending

During Disassembly

During Reassembly

Use a wrench to remove

Remove gasket only if worn or
damaged
Use appropriate pliers to remove

Use pliers to grip ball at the tip of 
the X-element
Use a wrench to remove

Be careful not to bend

Be careful not to bend

Clean seating surfaces between cover 
and body, coat threads (only LA21) with 
anti-seize, tighten to the proper torque

Insert securely into the 3 slots on the X-
element guide or cover (figure A)
Insert right side up making sure not to 
catch the guide or cover (figure B)
Tighten to the proper torque

Fix with Valve Seat and make sure X-
element can be inserted smoothly

Disassembly/Reassembly 

(to reassemble, follow procedures in reverse)

Summary of Contents for LA Series

Page 1: ...881 Nagasuna Noguchi Kakogawa Hyogo 675 8511 Japan Tel 81 0 79 422 1122 Fax 81 0 79 422 0112 INSTRUCTION MANUAL Keep this manual in a safe place for future reference THERMOSTATIC AIR VENTS FOR STEAM LA SERIES LA13 LA13L LA21 LA13 LA21 LA13L Manufacturer ...

Page 2: ... The three types of cautionary items above are very important for safety be sure to observe all of them as they relate to installation use maintenance and repair Furthermore TLV accepts no responsibility for any accidents or damage occurring as a result of failure to observe these precautions Indicates an urgent situation that poses a threat of death or serious injury Indicates a DANGER WARNING or...

Page 3: ...properly and DO NOT use this product outside the specification range Local regulations may restrict the use of this product to below the conditions quoted CAUTION Refer to the product nameplate for detailed specifications Maximum allowable pressure PMA and maximum allowable temperature TMA are PRESSURE SHELL DESIGN CONDITIONS NOT OPERATING CONDITIONS Tag No is displayed for products with options T...

Page 4: ...1 LA13L w r i e u t q w r y e u t q y u t o q w i e r 3 Configuration No 1 2 3 4 5 6 7 8 9 Description Body Cover X element Valve Seat Screen Nameplate Spring Clip Cover Gasket X element Guide LA13 LA13L LA13L ...

Page 5: ...creen Valve seat Spring Clip X element guide Cover gasket Cover gasket Screen Nameplate Nameplate X element X element Cover Cover Spring Clip 4 Exploded View LA13 LA21 LA13L Shown upside down for maintenance LA13 LA13L ...

Page 6: ...iveness of air removal also install an air vent in front of the steam using equipment 4 Install the air vent vertically LA13 LA21 with the arrow on the nameplate or body LA13L pointing in the direction of flow DO NOT install the air vent upside down 5 To protect people from hot air or steam from the outlet of the air vent connect a pipe leading to a pit but do not submerge the pipe in water this m...

Page 7: ...spection and Maintenance Installation inspection maintenance repairs disassembly adjustment and valve opening closing should be carried out only by trained maintenance personnel Before attempting to open the vent close the inlet isolation valve of the equipment and wait until the air vent has cooled to room temperature Failure to do so may result in burns or injury LA13L can be maintained without ...

Page 8: ...e seat Clean the valve seat or replace with a new valve seat LA13L or cover The screen is clogged Clean parts The air vent operating pressure exceeds the maximum specified pressure or there is insufficient pressure differential between the air vent inlet and outlet Compare specifications and actual operating conditions Cause Remedy Problem Part No Body 1 Cover 2 Cover Gasket 8 LA13 LA13L Replace w...

Page 9: ... SHIPMENT BY TLV Exclusive Remedy THE EXCLUSIVE REMEDY UNDER THIS WARRANTY UNDER ANY EXPRESS WARRANTY OR UNDER ANY IMPLIED WARRANTIES NOT NEGATED HEREBY INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE IS REPLACEMENT PROVIDED a THE CLAIMED DEFECT IS REPORTED TO TLV IN WRITING WITHIN THE APPLICABLE WARRANTY PERIOD INCLUDING A DETAILED WRITTEN DESCRIPTION OF T...

Page 10: ...IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE CANNOT BE EXCLUDED SUCH DAMAGES ARE EXPRESSLY LIMITED IN AMOUNT TO THE PURCHASE PRICE OF THE DEFECTIVE PRODUCT THIS EXCLUSION OF CONSEQUENTIAL AND INCIDENTAL DAMAGES AND THE PROVISION OF THIS WARRANTY LIMITING REMEDIES HEREUNDER TO REPLACEMENT ARE INDEPENDENT PROVISIONS AND ANY DETERMINATION THAT THE LIMITATION OF REMEDIES ...

Page 11: ... ...

Page 12: ...Printed on recycled paper Tel 81 0 79 422 1122 Fax 81 0 79 422 0112 Rev 9 2020 M PAC 65348 a 881 Nagasuna Noguchi Kakogawa Hyogo 675 8511 Japan Manufacturer ...

Reviews: