172-65427MA-05 (JH7RH-P/JH7RHT-P) 29 Sep 2016
11
Table of Tightening Torques
Part Name
Torque
Distance Across Flats
N
⋅
m
(lbf
⋅
ft)
mm
(in)
Cover Plug (JH7RH-P/JH7RHT-P)
100
(73)
26
(1)
Cover Nut
700
(510)
46
(1
13
/
16
)
Orifice Locknut
250
(185)
32
(1
1
/
4
)
Outlet Cover Nut
200
(150)
30
(1
3
/
16
)
NOTE: - Coat all threaded portions with anti-seize.
(1 N
⋅
m
≈
10 kg
⋅
cm)
-
If drawings or other special documentation were supplied for the
product, any torque given there takes precedence over values shown
here.
Special Notes
1. After operation following disassembly and reassembly, it is recommended that
the trap be let to sit for a day and then receive additional tightening.
2. Using the tightening torques for the
cover nuts and outlet cover nuts as a
reference, tighten until the cover and
outlet cover gaps are uniform. The gaps
should be 1.5 mm (
1
/
16
in) or less.
Cover or Outlet Cover
1.5 mm (
1
/
16
in)
Body