172-65188M-08 (
M-COS 3,16,21
Pressure Reducing Valve) 24 Jun 2015
23
<Valve>
Disassembling the Pilot Section
The diaphragm is removed by utilizing the notch in the pilot body. Loosen the pilot
valve seat with a box wrench and remove it. Lift the pilot valve spring up and out with
a pair of tweezers. Then loosen and remove the pilot screen holder to remove the
pilot screen.
→Check for any fault on the pilot valve seat, flaws on the gaskets and clogging of
the pilot screen.
Check for deformation, corrosion or faults on the diaphragm. The diaphragm
should be convex (open downward), with the printed “UP” mark on the top.
Notch
Diaphragm
Pilot Valve Seat
& Gasket
Pilot Cover
Bolt
Pilot Body
& Gasket
Pilot Screen
Pilot Screen Holder & Gasket
Pilot Valve
Pilot Valve Spring
Diaphragm
Pilot Valve Seat
& Gasket
Pilot Valve
Pilot Valve Spring
Notch
Bolt
Pilot Body
& Gasket
Pilot Screen
Pilot Screen Holder & Gasket
15 – 50 mm
65 – 100 mm