background image

4. Insert X

CHANGE

R

TM

hood backing plate through exterior wall with collars on inside of house. IMPORTANT: Make sure backing plate

bent flange is on top facing out, (See Diagram G). For vinyl or other types of lap siding, level backing plate and trace around 
edges. Trim siding back enough to install J channel or appropriate flashing, (See Diagram E). 

5. Place a bead of caulk on back side of hood backing plate or building sheathing before inserting backing plate, (See Diagram F).

6. Insert X

CHANGE

R

TM

hood backing plate through exterior wall. NOTE: It may be desirable to attach flex duct to collars and feed into 

house to make it easier to attach duct to collars if mounting through rim joist. IMPORTANT: Make sure that hood backing plate 
bent flange is on top facing out, level and secure to wall using (4) 1” sheetrock screws, (See Diagram G).

7. Install J channel or appropriate flashing around X

CHANGE

R

TM

hood backing plate. Do not cover up hood backing plate or 

hood may not fit in J channel, (See Diagram H).

8. Hook X2R hood on backing plate top bent flange, and install (4) 1/4” x 3/8” self tapping screws in bottom of hood through flange 

clearance holes to screw hood into backing plate, (See Diagram I).

9. Apply a bead of caulk around hood and siding, (See Diagram J).

10. Mount X2R Fan Assembly below or between joists / trusses to a cross brace or to a wall stud in any orientation with 

(3) 5/16” x 1 1/4” screws on left, right and center mounting feet, (See Diagram K).

11. Use 6” flex duct to connect X

CHANGE

R

TM

hood to fan assembly collars. Firmly secure duct to collars with included zip ties. 

Insulated flex should be used in cold climates to prevent condensation. Properly support duct to minimize sagging, bends and 
sharp turns that may restrict air flow, (See Diagram L).

5

DIAGRAM E

DIAGRAM F

LEVEL XCHANGER HOOD BACKING PLATE AND
TRACE FLANGE. TRIM SIDING BACK SO BACK-
ING PLATE CAN BE MOUNTED FLUSH TO EXTE-
RIOR SHEATHING.

PLACE A BEAD OF CAULK ON XCHANGER HOOD
BACKING PLATE FLANGE OR BUILDING SHEATH-
ING BEFORE INSERTING BACKING PLATE. 

DIAGRAM H

INSTALL J CHANNEL OR APPROPRIATE FLASHING
AROUND XCHANGER HOOD BACKING PLATE.

DIAGRAM K

MOUNT X2R BELOW OR BETWEEN JOISTS / TRUSSES TO A
CROSS BRACE OR ON A STUD WALL IN ANY ORIENTATION.
USE (3) 5/16” X 1 1/4” SCREWS ON LEFT, RIGHT AND CEN-
TER MOUNTING FEET.

DIAGRAM L

FIRMLY SECURE DUCT TO COLLARS WITH INCLUDED ZIP TIES. INSULATED FLEX 
SHOULD BE USED IN COLD CLIMATES TO PREVENT CONDENSATION. PROPERLY
SUPPORT DUCT TO MINIMIZE SAGGING, BENDS AND SHARP TURNS THAT MAY
RESTRICT AIR FLOW. 

NOTE:

USE OPTIONAL DT2-6 KIT IF DUCTING ON DISCHARGE.

DIAGRAM J

APPLY A BEAD OF CAULK AROUND HOOD AND
SIDING..

DIAGRAM G

LEVEL HOOD BACKING PLATE AND SECURE TO
WALL USING (4) SCREWS. 

IMPORTANT:

MAKE

SURE BENT FLANGE IS ON TOP FACING OUT.

DIAGRAM I

HOOK X2R HOOD ON BACKING PLATE TOP
FLANGE. INSTALL (4) 1/4” X 3/8” SELF TAP-
PING SCREWS IN BOTTOM HOOD FLANGE
CLEARANCE HOLES TO SCREW HOOD INTO
BACKING PLATE.

BENT FLANGE MUST BE
ON TOP AND FACE OUT

Summary of Contents for XCHANGER X2R

Page 1: ... reserved P N 8504202 THIS DEVICE MUST BE INSTALLED BY A QUALIFIED PERSON READ INSTRUCTIONS CAREFULLY PRIOR TO INSTALLATION AND OPERATION OF THE XCHANGER REV A 07 14 TJERNLUND PRODUCTS INC 1601 Ninth Street White Bear Lake MN 55110 6794 PHONE 800 255 4208 651 426 2993 FAX 651 426 9547 Visit our web site www tjernlund com ...

Page 2: ...ing carton Inspect thoroughly for hidden damage INSTALLATION RESTRICTIONS WARNING Improper installation adjustment alterations service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the equipment supplier WARNING Sufficient air is needed for proper combustion and exhausting of gases th...

Page 3: ... or needs of the occupants For example a family with smok ers may want to cycle the XCHANGERTM more frequently than a family of non smokers Another timed method may be to cycle the XCHANGERTM during peak usage of exhaust fans such as bathroom kitchen laundry or utility Outdoor air should be brought in at these peak times to help balance out pressure inside the house The XCHANGERTM can be cycled on...

Page 4: ...t exhaust air from mechanical room unless makeup air is also supplied or equipment in mechanical room is sealed combustion Carbon monoxide poisoning may result Use the optional DT2 6 6 duct take off kit so exhaust can be removed from outside the mechanical room if necessary It is required that the XCHANGERTM be installed in a location where it will not be directed at the occupants Do not discharge...

Page 5: ...t damage electrical wiring and other hidden utilities Using a 1 2 bit drill pilot holes noted on the template from inside through rim joist wall board siding etc keeping drill bit perpendicular to the wall 1 2 bit must be long enough to penetrate through exterior 3 Use a level to mark 4 holes drilled in step 2 and connect the holes on building exterior See Diagram C Use provided X2R oval template ...

Page 6: ... 16 x 1 1 4 screws on left right and center mounting feet See Diagram K 11 Use 6 flex duct to connect XCHANGERTM hood to fan assembly collars Firmly secure duct to collars with included zip ties Insulated flex should be used in cold climates to prevent condensation Properly support duct to minimize sagging bends and sharp turns that may restrict air flow See Diagram L 5 DIAGRAM E DIAGRAM F LEVEL X...

Page 7: ... was performed 4 Details of the problem LIMITED PARTS WARRANTY AND CLAIM PROCEDURE Tjernlund Products Inc warrants the components of the XCHANGERTM for one year from date of installation This warranty covers defects in material and workmanship This warranty does not cover normal maintenance transportation or installation charges for replacement parts or any other service calls or repairs This warr...

Page 8: ...pairing or replacing at our option any product which shall within the above stated warranty period be returned to Tjernlund Products Inc at the address listed below postage prepaid THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF AND TJERNLUND PRODUCTS INC EXPRESSLY DISCLAIMS LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING FROM THE USE OF THIS PRODUCT THIS W...

Reviews: