background image

2

Disconnect power supply to fans and/or accessory controls when reversing fan direction or servicing the X

CHANGE

R

TM

. Failure to do

so may result in personal injury and/or equipment damage.

Make certain the power source is adequate for the X

CHANGE

R

TM

requirements. Do not add the X

CHANGE

R

TM

to a circuit where the 

total electrical load is unknown.

TJERNLUND OPTIONAL DH2P DEHUMIDISTAT CONTROL MODULE OPERATION 

The DH2P control module includes an adjustable dehumidistat control which activates the fan(s) if the relative
humidity rises above the selected set-point. It is generally recommended to maintain a Relative Humidity (RH)
below 60% to inhibit mold growth. The dehumidistat can be turned fully clockwise to the ‘on’ position for con-
stant fan(s) operation or it can be turned fully counter-clockwise to ‘off’ during seasons or times when it is not
desired for the X

CHANGE

R

TM

fan(s) to run. Each fan can be independently turned on/off by its fan switch on control

module.

STANDARD PLUG-IN TIMER OPERATION

A standard adjustable timer can also be utilized for timed operation of the X

CHANGE

R

TM

fan(s). Plug timer into standard outlet and

plug X

CHANGE

R

TM

fans into wall timer. 

TJERNLUND OPTIONAL SCP SPEED CONTROL OPERATION

Tjernlund’s optional SCP speed control can be used to vary the speed of the X

CHANGE

R

TM

fans. Plug SCP speed control into stan-

dard outlet and plug X

CHANGE

R

TM

fans into SCP speed control.

RECOMMENDED PATTERNS OF OPERATION

If using the optional DH2P dehumidistat control, the X2R fans can be cycled automatically based on the relative humidity level of the
house or it can be operated based on recommendations below. It is generally recommended to maintain a Relative Humidity (RH)
below 60% to inhibit mold growth.

A standard plug-in wall timer can be programmed based on the lifestyle or needs of the occupants. For example, a family with smok-
ers may want to cycle the X

CHANGE

R

TM

more frequently than a family of non-smokers.

Another timed method may be to cycle the X

CHANGE

R

TM

during peak usage of exhaust fans, such as bathroom, kitchen, laundry or

utility. Outdoor air should be brought in at these peak times to help balance out pressure inside the house.

The X

CHANGE

R

TM

can be cycled on and off at regular intervals to periodically provide fresh air to the home, exhaust stale air or have

one fan bring air in and the other fan exhaust air for a balanced air exchange. It can also be ran like an economizer to bring outside
air in during evening time when it is cooler outside.

HYPOTHETICAL XCHANGER OPERATION BASED ON LIFESTYLE

The example below shows a possible way in which cycling times of the X

CHANGE

R

TM

may be determined based on household 

occupant lifestyles.

6:00 A.M. to 9:00 A.M.

= Outside fresh air should be brought into the house to compensate for morning routines. Bathing, cooking,

laundry and other activities such as smoking necessitate that outside fresh air to be brought in. Depressurization of the house at these
times is common with many exhaust fans running at one time.

9:00 A.M. to 4:00 P.M.

= House is normally vacant with occupants at work or school. Cycle X

CHANGE

R

TM

on and off for 15 minute

intervals per hour to assure fresh air is supplied to the house.

4:00 P.M. to 8:00 P.M.

= Outside fresh air should be brought into the house to compensate for evening routines. Bathing, cooking,

laundry and other activities such as smoking necessitate that outside fresh air to be brought in. Depressurization of the house at these
times is common with many exhaust fans running at one time.

8:00 P.M. to 6:00 A.M.

= All members of the household are usually present. Outside fresh air is needed to dilute occupant generated

carbon dioxide during sleeping. Cycle X

CHANGE

R

TM

on and off for 15 minute intervals, with occasional 30 minute intervals to assure

fresh air is supplied to house.

Summary of Contents for XCHANGER X2R

Page 1: ... reserved P N 8504202 THIS DEVICE MUST BE INSTALLED BY A QUALIFIED PERSON READ INSTRUCTIONS CAREFULLY PRIOR TO INSTALLATION AND OPERATION OF THE XCHANGER REV A 07 14 TJERNLUND PRODUCTS INC 1601 Ninth Street White Bear Lake MN 55110 6794 PHONE 800 255 4208 651 426 2993 FAX 651 426 9547 Visit our web site www tjernlund com ...

Page 2: ...ing carton Inspect thoroughly for hidden damage INSTALLATION RESTRICTIONS WARNING Improper installation adjustment alterations service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the equipment supplier WARNING Sufficient air is needed for proper combustion and exhausting of gases th...

Page 3: ... or needs of the occupants For example a family with smok ers may want to cycle the XCHANGERTM more frequently than a family of non smokers Another timed method may be to cycle the XCHANGERTM during peak usage of exhaust fans such as bathroom kitchen laundry or utility Outdoor air should be brought in at these peak times to help balance out pressure inside the house The XCHANGERTM can be cycled on...

Page 4: ...t exhaust air from mechanical room unless makeup air is also supplied or equipment in mechanical room is sealed combustion Carbon monoxide poisoning may result Use the optional DT2 6 6 duct take off kit so exhaust can be removed from outside the mechanical room if necessary It is required that the XCHANGERTM be installed in a location where it will not be directed at the occupants Do not discharge...

Page 5: ...t damage electrical wiring and other hidden utilities Using a 1 2 bit drill pilot holes noted on the template from inside through rim joist wall board siding etc keeping drill bit perpendicular to the wall 1 2 bit must be long enough to penetrate through exterior 3 Use a level to mark 4 holes drilled in step 2 and connect the holes on building exterior See Diagram C Use provided X2R oval template ...

Page 6: ... 16 x 1 1 4 screws on left right and center mounting feet See Diagram K 11 Use 6 flex duct to connect XCHANGERTM hood to fan assembly collars Firmly secure duct to collars with included zip ties Insulated flex should be used in cold climates to prevent condensation Properly support duct to minimize sagging bends and sharp turns that may restrict air flow See Diagram L 5 DIAGRAM E DIAGRAM F LEVEL X...

Page 7: ... was performed 4 Details of the problem LIMITED PARTS WARRANTY AND CLAIM PROCEDURE Tjernlund Products Inc warrants the components of the XCHANGERTM for one year from date of installation This warranty covers defects in material and workmanship This warranty does not cover normal maintenance transportation or installation charges for replacement parts or any other service calls or repairs This warr...

Page 8: ...pairing or replacing at our option any product which shall within the above stated warranty period be returned to Tjernlund Products Inc at the address listed below postage prepaid THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF AND TJERNLUND PRODUCTS INC EXPRESSLY DISCLAIMS LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING FROM THE USE OF THIS PRODUCT THIS W...

Reviews: