Copyright © 1998, Tjernlund Products, Inc.  All rights reserved

P/N 8504075

OWNER INSTRUCTIONS, DO NOT DESTROY

Recognize this symbol as an indication of important safety information!

NOTE: MAXIMUM FLUE GAS TEMPERATURES MUST NOT EXCEED 650oF.  

THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE
PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS
UNIT.   READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLA-
TION OR OPERATION.  FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN
IMPROPER INSTALLATION,  ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY
RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLO-
SION, PERSONAL INJURY OR PROPERTY DAMAGE.

!

DO NOT DESTROY.  PLEASE READ CAREFULLY AND

KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

MODEL SS2G

INSTALLATION INSTRUCTIONS

REV. 1 11/98

56826

TJERNLUND PRODUCTS, INC.

1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com

Summary of Contents for SS2G SIDESHOT (DISCONTINUED) 8504075 REV 1 1198

Page 1: ... INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLA TION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUSTMENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRICAL SHOCK CARBON MONOXIDE POISONING EXPLO SION PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE MODEL SS2G INSTALLATION ...

Page 2: ...s heating equipment It is factory assem bled and wired The SS2G automatically vents the flue gases from heating equipment to the outdoors By recirculating indoor air with a cooling fan surrounding combustible materials remain at safe temperatures After each burner cycle the SS2G will continue to operate for a nonadjustable timed period of approximately 45 seconds to purge the heater and vent of re...

Page 3: ... through the Fan Proving Switch must not exceed its nameplate ratings 5 Vent runs of over 15 linear feet require the use of an approved insulated vent connector to prevent problems related to condensation CAUTIONS The Power Venter must be installed by a qualified installer in accordance with these instructions and all local codes or in their absence in accordance with the latest edition of The Nat...

Page 4: ...hould be recognized that generalized proce dures cannot anticipate all situations Accordingly in some cases deviation from this procedure may be necessary to determine safe operation of the equipment a Perform this procedure prior to any attempt at modifications of the appliance or installation of the SS2G b If it is determined there is a condition which could result in unsafe operation shut off t...

Page 5: ...jeopardize people overheat combustible structures or enter buildings Not to be less than 10 feet from an adjacent building The SS2G is also Listed to terminate a minimum of 12 inches from soffits decks or adjacent sidewalls It is not recommended for the SS2G to be terminated on a wall that faces the direction of the prevailing winds Backdrafts by severe winds can interrupt equipment operation 4 DI...

Page 6: ...e rectangular opening should be no larger than 10 1 2 in width by 8 1 2 in height See Diagram C 6 Knock out block material exposing rectangular opening through the wall DIAGRAM C INSTALLING SS2G VENT CABINET 1 a Fold SS2G Vent Cabinet template Page 14 along dashed line and attach between the floor joists ensuring that it is snug against the sill plate and centered between the floor joists Follow s...

Page 7: ... isolation Use the prepunched holes on the wall bracket as a template to mark holes to be drilled into the side wall for mounting screws See Diagram H 4 a If installing the bracket into a wood wall drill 2 pilot holes at each point established in step 3 with a 1 8 drill bit approximately 1 deep and install the screws provided to secure the bracket to the wall b If installing the bracket into a mas...

Page 8: ...round inlet pipe from box 2 Align the 4 slots of the inlet pipe to the 3 pins and proving switch sensing tube push pipe up until it bottoms out in the SS2G inlet 3 Turn the inlet collar clockwise to lock in place See Diagram I IMPORTANT After vent pipe is installed verify inlet pipe is locked tightly in place INSTALLATION OF VENT PIPE The SS2G inlet is designed to accept 4 single wall or type B ve...

Page 9: ...is energized Normal combustion sequence for the furnace begins induced draft furnace blower starts its proving switch makes energizing ignition control and or gas valve DO NOT OPERATE THE FURNACE WITHOUT THE FAN PROVING SWITCH WIRED INTO THE 24V FURNACE CIRCUIT NOTE When Power Venter is interlocked with a thermostat wire all zones circulators and limits as would normally be done if venting into a ...

Page 10: ...9 ...

Page 11: ...h fire If the draft appears excessive turn the draft adjustment knob counterclockwise and repeat steps A through C 4 Lock the draft adjustment knob in place by tightening the locking nut behind the bracket See Diagram K 5 Turn off appliances and exhaust fans activated for draft adjustment procedure DIAGRAM K COMBUSTION AIR Adequate combustion air is vital for proper combustion and for safe venting...

Page 12: ...ss W C at thermostat No call for heat Contact Tjernlund Products Inc for additional assistance 24 Volts present Step 1 Confirm that thermostat is not calling for heat Step 2 With the Power Venter running remove the ORANGE wire on Relay Timer terminal 5 Result Power Venter should shut off within approximately 45 seconds Yes 24 Volts not present SYMPTOM 2 POWER VENTER DOES NOT RUN DURING CALL FOR HE...

Page 13: ... to SS2G Check Fan Proving Switch tube for clear passage Step 5 Remove call for heat to SS2G Remove the BLUE and YELLOW wires from SS2G Proving Switch Activate thermostat to call for heat With SS2G running check for continuity across the COM and N O terminals of Fan Proving Switch Result Contacts on switch should be closed Step 7 Reset the SS2G High Limit by depressing the button located on the ce...

Page 14: ...rnlund distributor for replacement Please include SideShot date code component was taken from The date code is located on the Electrical Box coverplate If the date code is older than 30 months you will need to provide a copy of the original installation receipt to your distributor Credit or replacement will only be issued to a Tjernlund distributor after the defective part has been returned prepai...