background image

SS1R WITH INTEGRAL UC1 UNIVERSAL CONTROL BOARD FEATURES

# 1.

Power supplied by board.  Do not supply power to this area or control damage may result.

# 2.  Do not supply power to the appliance interlock block with the call selector in the “DRY” position.  

Control damage may result if power is supplied.

# 3.  Circuit protection must be provided by the installer.  16 Amps is the maximum current allowed for this device at terminal L.

VETI

A 15 Amp circuit breaker is recommended.

VETI

I

PRE / POST PURGE AND PROVER STATUS CHECK DIP SWITCH SETTINGS

Remove power to SS1R and heating equipment when installing, servicing or changing dip switch settings. Failure to do so may result in 
personal injury and/or equipment damage.  LED #6 (RED) should not be on if 115 VAC supply power is removed from the control.

Pre-purge 

Used for longer vent runs to get draft fully established throughout the vent system prior to burner ignition.  Also beneficial for nega-
tive pressure prone environments.

IMPORTANT:

Nuisance equipment lockouts may occur if our pre-purge is running in conjunc-

tion with and is longer than any equipment timing circuit.  Pre-purge settings must be shorter than burner control lockout time
unless wired prior to burner control timing circuit (i.e. aquastat / thermostat).

Post-purge

A Venter post-purge has been factory set at 2 minutes.  Confirm that dip switch #5 is in the up or "on" position.  Oil fired equipment
requires that the post-purge be long enough to eliminate post cycle nozzle drip odor. A longer post-purge may be necessary for
longer vent runs or high heat retention, refractory lined combustion chambers.  

4

LED 1 (AMBER)
LED 2 (BLUE)
LED 3 (GREEN)
LED 4 (RED)
LED 5 (RED)

LED 6 (RED) POWER LED

DRY 

24 V

115 V

APPLIANCE
INTERLOCK

RELAY

VENTER

MOTOR

RELAY

A B   1   2   3   4   L N 

J1    J2       XL    XN

P1   P2    C   GND   F

(1            9)

N     M    MTR    

XL / XN AUXILIARY DEVICE 
POWER TERMINALS 

115 VAC - Maximum of 0.15 Amps.
Only connect to Tjernlund auxiliary devices.

SEE WARNING # 1.

LED STATUS LIGHTS

See “LED Status & Fault
Indicator Section” for details.

J1- J2 CALL 
JUMPER

Used when the call signal is
used as the “proven” return
signal to the appliance.  See
wiring section for details.

APPLIANCE INTERLOCK 
TERMINAL BLOCK (A-B, 1-4)
A - B

- Dry Contact call. 3 mA @ 5VDC.

SEE WARNING # 1.

1

- 24 or 115 VAC intercepted call.  

IMPORTANT

: RED voltage jumper must 

match intercepted call voltage.

2

- 24V common or 115V Neutral.

3

- Common terminal to appliance relay con-

tacts.  

IMPORTANT:

J1-J2 jumper routes 

call voltage at terminal 1 to 3.  Remove 
J1-J2 jumper if a different voltage source is 
provided to terminal 3.

4

- Normally open terminal of appliance relay.  

Will be energized from terminal 3 if safety 
circuit is “proven”. 

L / N - 115 VAC POWER 
SUPPLY BLOCK

115 VAC / 50-60 Hz
Circuit protection provided by installer.

SEE WARNING # 3.

MTR & M LOAD TERMINALS 
FROM VENTER MOTOR RELAY

Used to drive SS1R Motor & Burner Motor. 
1 HP MAX LOAD across terminals MTR & M / N.  

APPLIANCE INTERLOCK
RELAY

1 HP MAX LOAD across 
terminals 3 & 4.

VENTER MOTOR RELAY

1 HP MAX LOAD from 
terminals L to MTR & M.

P1 - P2 SAFETY CIRCUIT
TERMINALS

1 mA @ 5VDC.

SEE WARNING # 1

.

C, GND, F AUXILIARY DEVICE 
COMMUNICATION TERMINALS

2 mA @ 5VDC.  For Tjernlund MAC1E or 
MAC4E auxiliary devices. 

SEE WARNING # 1

.

APPLIANCE CALL 
VOLTAGE SELECTION

Place 

RED

voltage jumper in

proper location based on
appliance call interlock volt-
age.  

SEE WARNING # 2.

IMPORTANT

DIP SWITCH SETTINGS

Pre-Purge (1-2)
Post-Purge (3-8) 
Prover status check (9)
See “Pre / Post Purge &
Prover Status Check Dip
Switch Settings”. 

Summary of Contents for SS1R SIDESHOT (DISCONTINUED VERSION-PRE UC1 UNIVERSAL CONTROL) 8504046 REV 0595

Page 1: ...RSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OF THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION OR PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE RE...

Page 2: ...ud Weatherking and Heat Controller oil fired furnaces The SS1R automatically vents the flue gases away from the oil furnace to the outdoors By combining outside air with high tech insulation and maintaining required clearances surrounding combustible materials remain at safe temperatures A factory post purge time is set at 2 minutes and is adjustable up to 16 minutes see Pre Post purge Settings on...

Page 3: ...he Canadian Electrical Code 2 Plan the vent layout so that the code required clearances are maintained from plumbing wiring and combustible materials 3 The SS1R motor shaft must be mounted horizontally to ensure proper operation of the Fan Proving Switch and prevent motor bearing wear 4 Flue gas temperatures must not exceed 575oF at SS1R inlet Ambient temperature must not exceed 104oF 5 Make certa...

Page 4: ...mes Fan Prover was in electrically closed position prior to venter operation LED 4 Flashes 3 Times Fan Prover does not close within 60 seconds after call for heat LED 4 Flashes 4 Times Fan Prover did not re close after 10 minutes of Venter operation LED 4 Flashes 5 Times Fan Prover opened for more than 10 seconds during burner cycle but closed within 10 minutes Investigate causes of Fan Prover not...

Page 5: ... LED 2 BLUE LED 3 GREEN LED 4 RED LED 5 RED LED 6 RED POWER LED DRY 24 V 115 V APPLIANCE INTERLOCK RELAY VENTER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR XL XN AUXILIARY DEVICE POWER TERMINALS 115 VAC Maximum of 0 15 Amps Only connect to Tjernlund auxiliary devices SEE WARNING 1 LED STATUS LIGHTS See LED Status Fault Indicator Section for details J1 J2 CALL JUMPER Used when...

Page 6: ...ings Not to be less than 2 feet from an adjacent building The SS1R is also Listed to terminate a minimum of 12 below above or horizontally from a soffit deck or adjacent sidewall Pre Purge Post Purge Pre Cycle Prover Status Check Deactivated DIP SWITCH NUMBERING 1 ON 2 3 4 5 6 7 8 9 ON PRE PURGE SETTINGS SEE PRE PURGE ON PAGE 4 PRIOR TO SETTING 1 2 1 2 1 2 1 2 0 Seconds 5 Seconds 20 Seconds 35 Sec...

Page 7: ...pardize people overheat combustible structures or enter buildings A venting system shall not terminate within 1 8 m 6ft of the following A window door or mechanical air supply inlet of any building including soffit openings A gas service regulator vent outlet A combustion air inlet A property line A direction facing combustible materials or openings of surrounding buildings A venting system shall ...

Page 8: ...e from rim joist and attach to building exterior aligning pilot hole markings on template with holes previously created in Step 2 4 Drill the four corner holes noted on the template through the building exterior Remove the template and mark lines from the outside edge of the holes drilled forming a rectangle 5 Using reciprocating saw and appropriate blade cut a rectangular open ing through the rim...

Page 9: ...Template B to the floor joist that is to be notched aligning the sight line noted on the template with the end or the outside casing of the Vent Hood Terminus 2 Cut out notch on line shown on the template NOTCH BRACING It is recommended and local codes may dictate that the joist be reinforced as outlined below Bracing of the rim joist is not necessary 1 Cut two 2 x 4 pieces of wood 28 inches in le...

Page 10: ... drill bit approximately 1 deep and install the screws provided to secure the bracket to the wall b If installing the bracket into a masonry wall drill 2 holes at each point established in step 3 with a 1 4 masonry drill bit approximately 1 deep Tap the masonry anchors into the holes drilled in step 4 Screw the wall bracket onto the wall 5 Connect the other end of wall support bracket to the stud ...

Page 11: ... metal tube 5 Attach the vent pipe inlet collar to the rear inlet port making sure that the sensing tube is orientated as shown See Diagram M NOTE Alignment marks on the inlet collar and plenum casing must match 6 Attach 90 0 compression fitting to the short tube on the inlet collar 7 Using the soft aluminum tubing connect the Fan Proving Switch to the inlet collar Take care not to crimp the tubin...

Page 12: ... INSTRUCTIONS PERTAIN ONLY TO RHEEM RUUD OR WEATHERKING D OBD XXX OPD XXX and etc and F OBF XXX OPF XXX and etc SERIES OIL BURNING FURNACES 1 All wiring from the SS1R to the oil furnace must be appropriate Class 1 wiring as follows installed in a rigid metal conduit intermediate metal conduit rigid non metal conduit electrical metallic tubing Type MI Cable Type MC Cable or be otherwise suitably pr...

Page 13: ...ld be routed through a disconnect so that power to the SS1R can be turned off remotely if necessary Additionally all wire should be run through the appropriate conduit per NEC standards as noted in step 1 C A ground wire will need to be installed between the system ground and the grounding lug in SS1R electrical box D A neutral wire will need to be installed from the oil furnace line neutral to th...

Page 14: ...equire a special male quick connect Amp Manufacturing part 2 520102 2 insulated male spade Do NOT cut any wires on the existing burner Also the wire connection to the Burner Motor lead should be made inside the burner junction box and should be covered and concealed by the primary control once it is replaced G Install a field constructed wire between the terminal labeled Burner Motor step E above ...

Page 15: ...ICE In order for the SS1R pressure switch to function properly for the intended application the proper bleed orifice has to be selected as determined below 1 Upon installation if the furnace input rate is 1 gallon per hour or less 140 000 BTU hr or less then the plug should be installed in the pressure switch 2 Upon installation if the furnace input rate is greater than 1 gallon per hour or 140 00...

Page 16: ...uipment to operate for at least five minutes Tripping of the burner circuit by the Fan Prover Switch or Limit during the five minute operation indicates an unsafe operating condition Turn fuel supply off to appliance and DO NOT OPERATE UNTIL UNSAFE VENTING CONDITION IS INVESTIGATED BY QUALIFIED SERVICE PERSONNEL 6 Turn thermostat to the off position Verify the SS1R and the burner operate for sever...

Page 17: ...OTING ELECTRICAL PROBLEMS The following guide is intended to be used if a problem occurs during the use of the SS1R sidewall vent system It may be necessary to measure voltage during troubleshooting Extreme caution must be exercised to prevent injury If you are unable to determine the defective part with the use of this guide call your Tjernlund distributor or Tjernlund Products direct at 1 800 25...

Page 18: ...post purge may cause limit to trip If the limit switch trips verify that the post purge setting is long enough to remove residual heat from the combustion chamber If high limit will not reset and has an open circuit replace high limit part number 950 0640 If high limit trips repeatedly do not operate the heater until the source of excessive heat has been determined and repaired For any newly estab...

Page 19: ...nput and vent pipe lengths are not exceeded See Application Table on page 1 for capacities Check fan proving switch sensing tube for blockage Yes measured draft is at least 0 07 w c Replace fan proving switch part number 950 0750 MAINTENANCE SERVICE TECHNICIAN AND USER REQUIREMENTS 1 SS1R must be visually inspected annually 2 Verify over fire draft CO2 and smoke readings are all correct See Draft ...

Page 20: ...eries Wheel 950 0635 SS1R Proving Switch 950 0750 High Limit Switch 950 0640 UC1 Universal Control Circuit Board 950 8804 Oil Solenoid For D series oil furnaces OBD XXX OPD XXX and etc 950 0690 Oil Solenoid For F series oil furnaces OBF XXX OPF XXX and etc Contact Rheem Prostock parts department for solenoid part number WHAT IS NOT COVERED Product installed contrary to our installation instruction...

Page 21: ...20 SIGHT LINE LINE SIGHT TEMPLATE B C U T O U T B O U N D A R Y C U T O U T B O U N DARY ...

Page 22: ...BACKSIDE OF TEMPLATE B ...

Page 23: ...21 CORNER HOLES TEMPLATE A PILOT HOLES CORNER HOLES INSTRUCTIONS Rough in 8 3 8 Width 8 Height 8 Height 8 3 8 Width Rough in ...

Reviews: