For the commissioning settings to be stored the unit needs to be powered up.
Continuous Supply & Extract Speeds:
1. Move Program/Run Switch to
Continuous position.
2. Rotate supply fan Continuous
Speed adjustment potentiometer
to achieve required supply
continuous air flow.
3. Rotate extract fan Continuous
Speed adjustment potentiometer
to achieve required extract
continuous air flow.
4. Return Program/Run Switch
to centre position to exit
commissioning.
Boost Supply & Extract Speeds:
1. Move Program/ Run Switch to Boost position.
2. Rotate supply fan Boost Speed adjustment potentiometer to achieve required
supply boost air flow.
3. Rotate extract fan Boost Speed adjustment potentiometer to achieve required
extract boost air flow.
4. Return Program/Run Switch to centre position to exit commissioning.
Boost Overrun
Boost Overrun Timer is variable between
0 and 60 minutes. Rotate potentiometer
to change overrun time. This can be
done at any time.
Boost
Overrun
Timer
Program
Switch
Run
Continuous
Boost
Boost Overrun Timer
Extract
Supply
Potentiometers
Extract
Supply
BP
40262/099
Boost
Cont
1
2
3
4
5
6
7
8
0
60
30
DO 4937 iss 01
Commissioning Pot positions
Boost
Overrun
Timer
Program
Switch
Run
Continuous
Boost
Boost Overrun Timer
Extract
Supply
Potentiometers
Extract
Supply
BP
40262/099
Boost
Cont
1
2
3
4
5
6
7
8
0
60
30
DO 4937 iss 01