10
Continuation table 8
1
2
3
64
TRAF. L. BOT OUT 2
The Road Blocker2
DOWN
position output.
It is active when the Road Blocker1 is in DOWN position.
It is inactive when the Road Blocker1 is not in DOWN position.
It can be used by access control system or for traffic light relay control.
65
OUT 2
The Road Blocker 2
accumulator valve
control output. It is used only in
the road blockers with accumulator.
66
+ INDICATION LED 2
Output for connection of the Road Blocker 2 additional
LED 1
display
module
anode "+"
.
67
- INDICATION LED 2
Output for connection of the Road Blocker 2 additional
LED 1
display
module
cathode"-"
.
All outputs but
INDICATION LED
include similar interface of
"open collector"
type.
The load capacity of outputs
59.INDICATION RED 2, 60.INDICATION GREEN 2, 61.SOUND 2
is
1,5 А
.
The load capacity of outputs
63.TRAF.L.TOP OUT 2, 64. TRAF.L.BOT OUT 2, 65. SOUND 2
is
0,2 А.
The output status is indicated by displays
LED27-LED32
located next to them.
Connection to terminal blocks is performed via the additional intermediate terminal block
B3-TX3.
Connection block OUT2 Wago 260
.
Table 9
contains description of terminal block
X9. RS485
The Road blocker 1
and
2
remote control panel
RB111
and angular position sensors
DI-601
to be
connected to terminal block
X9. RS485
–
Interface RS485
.
Item Terminal name
Purpose
38
+12VDC
+12VDC
power voltage of remote control panel
DI-601
39
RS485 A1
Signal
RS485 A
of angular position sensors
DI-601
40
RS485 B1
Signal
RS485 B
of angular position sensors
DI-601
41
GND
Common wire
GND
of angular position sensors
DI-601
42
+12VDC
+12VDC
power voltage of remote control panel
RB111
43
RS485 A2
Signal
RS485 A
of remote control panel
RB111
44
RS485 B2
Signal
RS485 B
of remote control panel
RB111
45
GND
Common wire
GND
of remote control panel
RB111
The remote control panel
RB111
can be located at a distance of up to
500
meters from
control unit. If distance from the remote control panel
RB111
to control unit is less than
50 m
, then
any cable with wire section
4х0,22
can be used for connection.
When distance is more than
50 m
, then cable
UTP
or
FTP 4x2x0,51
to be used. In this case two
wires of one twisted pair to be used for signals
RS485 A
and
RS485 B
.
When
two road blockers
are used with
one control unit
, then the Road Blocker 1 and 2 angular
position sensors
DI-601
to be connected to terminals
42-45
of terminal block
X9. RS485
in parallel.
Addresses of the Road Blocker1 and 2 angular position sensors
DI-601
are different -
1
and
2
respectively.
Sensor address is indicated on
inspection box
of Road Blocker electrical connections and on the
sensor
DI-601
itself.
The angular position sensors
DI-601
are used only in the Road Blockers of “
High Security Road
Blocker
”, “
Cyclope
”, “
Speedbump
” types.
In the Road Blo
ckers of “Bollard”, “
Tire
Killer”, “Boom Barrier” types
magnetic limit switches are used as
end position sensors.