INSTALLATION

 

 

The Model 2601 is a socket-mounted voltage sensing 
relay.  The pin configuration diagram, below and on the 
unit, shows the contacts in the power off or tripped 
condition.  Connect the wiring to the socket as shown in 
the Typical Application Diagram.  

Observe the proper 

polarity of the input voltage for DC models

 

PIN DIAGRAM 

 

 
 
 
 
 
 
 
 

ADJUSTMENT PROCEDURE

 

 

NOTE:

  When adjusting the Model 2601 you may wish 

to jumper the control circuit contacts to prevent tripping 
the load on and off.  A variable voltage source and a 
digital voltmeter provide the most accurate means of 
calibrating the trip point.

 

 

For under voltage sensing

, slowly rotate the 

adjustment pot  counter clockwise  until the indicator 
light just illuminates and the contacts transfer.  Any 
voltage below this level will now trip the relay. 
 
A reasonably accurate voltage setting can be obtained 
by using only the operating line voltage.  Apply the 
voltage and follow the adjustment procedure above.  
Any voltage approximately 2% to 4% below the nominal 
voltage will now trip the relay.  To prevent nuisance 
tripping you may need to turn the adjustments slightly 
lower as needed.

 

 

WARRANTY

 

 

The 

Model 2601 Voltage Sensor 

is covered by Time 

Mark Corporation’s exclusive 

5-Year Unconditional 

Warranty

.  Should  this device fail, for any reason, 

within five years from the date of purchase, we will 
repair or replace it free.  Contact the Time Mark Sales 
department, Monday through Friday; 8 a.m. to 5 p.m., 
CST, for further details. 

TYPICAL APPLICATION 

Model 2601 

MODEL 2601

 

Voltage Sensor

 

READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING  THIS DEVICE. 

KEEP THIS DATA SHEET FOR FUTURE REFERENCE. 

 

GENERAL SAFETY

 

 

POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 2601.

 

ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING. 

THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL. 

 

Installation Instructions 

 

NOTE:   

When installing the Model 2601 in areas of high 

humidity or contamination, the base area and all exposed 
metal parts of  the socket should be coated with a good 
quality silicon grease such as Dow Corning* DC-4 or DC-4x.  
Insert the relay into the socket and wipe off excess grease 
from around the base.  This will help prevent moisture and 
other contaminants from entering the base and socket areas.

 

TIME MARK is a division of

Telephone:    Main -     (918) 438-1220 
                        Sales -    (800) 862-2875

 

Fax:                                 (918) 437-7584 
 
E-mail:            [email protected] 
Internet:         http://www.time-mark.com 

Doc No. 87A167   12/00 

© 2000   

TIME MARK CORPORATION

 

11440 East Pine Street  

Tulsa, Oklahoma  74116 

Shows No Power Applied 

Summary of Contents for 2629

Page 1: ...ts Input voltages above the setpoint cause the output contacts to energize Input voltages below the setpoint cause the output contacts to de energize The dead band between pull in and drop out is less...

Page 2: ...allows the unit to be set to detect over voltage relay will energize on fault The L E D indicator will illuminate whenever the relay is energized NOTE When installing the Model 2629 Voltage Monitor i...

Page 3: ...ction 2500 VRMS for 10 msecs Polarity protection not required Supply current 10mA max Setpoint stability 1 Response time 100 msecs Operation Continuous duty Output contacts SPDT 10 Amps at 240 VAC res...

Page 4: ...E CERTAIN TO USE THE TIME MARK MODEL 51X120 8 PIN SOCKET OR AN EQUIVALENT UL APPROVED 600VAC RATED SOCKET MODEL 260 Voltage Sensor READ ALL INSTRUCTIONS BEFORE INSTALLING OPERATING OR SERVICING THIS D...

Page 5: ...220 Sales 800 862 2875 Fax 918 437 7584 E mail sales time mark com Internet http www time mark com Doc No 87A167 12 00 2000 TIME MARK CORPORATION 11440 East Pine Street Tulsa Oklahoma 74116 SPECIFICAT...

Page 6: ...rk Corporation s exclusive 5 Year Unconditional Warranty Should this device fail for any reason within five years from the date of purchase we will repair or replace it free Contact the Time Mark Sale...

Page 7: ...no field adjustments or calibrations to the device MODEL 2602 Nominal input voltage 120 VAC Max input voltage 135 VAC Frequency 60 Hz Power consumption 2 watts max Drop out voltage 80 VAC Pick up vol...

Page 8: ...PERATING OR SERVICING THIS DEVICE KEEP THIS DATA SHEET FOR FUTURE REFERENCE GENERAL SAFETY POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 2602 ALL ELECTRICAL POWER SHOULD BE...

Page 9: ...to energize Input voltages below the setpoint cause the output contacts to de energize The dead band between pull in and drop out is less than 5 Dip switches are used on the Model 2628 to choose betwe...

Page 10: ...voltage relay will energize on fault The L E D indicator will illuminate whenever the relay is energized NOTE When installing the Model 2628 Voltage Monitor in areas of high humidity or contamination...

Page 11: ...stment range Over voltage 120 140 VAC Under voltage 90 110 VAC Response time 50 msec Line frequency 45 420 Hz Transient protection 2500V for 10 msec Contacts SPDT Contact rating 10A at 240 VAC resisti...

Page 12: ...ce WARRANTY The Model 268 Over Under Voltage Monitor is warranted to be free from defects in materials and workmanship and is covered by our exclusive 5 year Unconditional Warranty If this device fail...

Page 13: ...ltage 12vdc 24vdc 28vdc 48vdc 110vdc 230vdc Max input voltage 17vdc 32vdc 37vdc 62vdc 145vdc 270vdc Under voltage range 10 12vdc 19 24vdc 22 28vdc 38 48vdc 85 110vdc 175 230vdc Over voltage range 12 1...

Page 14: ...TROUBLESHOOTING Should the Model 2681 fail to operate properly check that voltage is present and is of the correct level Check all fuses and verify that all wiring connections are correct Should probl...

Page 15: ...sensing circuit drives an internal electro mechanical relay which is energized when the line fre quency is correct Operating power is drawn from the same line being monitored The Model 292 is set to t...

Page 16: ...mplete warranty details see the Terms and Con ditions of Sales page in the front section of the Time Mark catalog MODEL 292 Frequency Monitor READ ALL INSTRUCTIONS BEFORE INSTALLING OPERATING OR SERVI...

Page 17: ...phase Monitoring Current 1 mA max 120V per phase Voltage Adjustment Range 79 140VAC drop out pick up Frequency Adjustment Range 45 65 Hz Reset Type Automatic Repeat Accuracy 1 of full scale Output Con...

Page 18: ...ply power If the green LED is not on and the contacts do not transfer when power is applied check that all three phases are the correct voltage and are in the proper sequence A B C Check the 24VDC to...

Page 19: ...22 29vdc 25 34vdc 43 58vdc 99 135vdc 2621 ALL VERSIONS Power consumption 2 watts max Set point stability 0 5 of set point Polarity protection DC versions only Trip response 0 5 sec fixed 0 1 sec Reset...

Page 20: ...etails NOTE When installing the Model 2621 monitor in areas of high humidity or contamination it is recommended that the base area and all exposed metal parts of the socket be coated liberally with a...

Page 21: ...V Frequency 50 400 Hz Short Cycle Delay Short cycle restart delay 2 seconds R versions 5 minutes Set point Stability 1 Dead Band 1 Trip Delay 0 5 seconds fixed Contact Rating SPDT 10A at 240VAC resist...

Page 22: ...tment until the failure indicator light just illuminates and the contacts transfer Any voltage below this point will trip the relay off For over voltage sensing Slowly rotate the adjustment until the...

Reviews: